Heat Pump (2 Stage Heat / 1 Stage Cool) 

 

24VAC Common

24VAC "HOT"

Auxilirary Heat

Compressor

Ground Fault

Fan

Compressor Relay

Aux Heat Relay

Fan Relay

Fault Relay

Reversing Valve

Energized in Cool

Energized in Heat

24VAC
CONTROL
TRANSMFOMER

THERMOSTAT

UP

HVAC SYSTEM

7
6

8

3

1

(G)

(Y1)

(B)

(C)

(RC)

4

5

9

(O)

(W2)

(L)

 

 

Figure 7

 

 

Connections for heat pump thermostat

 

 

 
CONFIGURATION 

 

 

The “System Type” for this thermostat must be set to “Heat Pump” under 

“System Options”

 

The “System Type” for this thermostat must be set to “Dual Fuel Heat Pump” for a dual fuel system 

(Terminal “W2” is connected to the “W” or “W1” on the furnace). 

 
POWER UP  

 

1.

 

Double check wiring, be sure that there

 

are

 

no stray wires or wire strands at the connections. 

2.

 

Connect power to the transformer and system.  The display will show all of the thermostat settings. 

3.

 

Press [FAN] and select “On”.  The fan should come on.   

4.

 

Press [FAN] and select “Auto”.  The fan should go off. 

5.

 

Press [HOLD] and select “On” to override Energy Efficient Control. 

6.

 

Set the Mode to "Heat".  Raise the desired heat setting 1 degree above the current temperature.  Ensure 
that the heat pump comes on, in heating mode.  After a few minutes, raise the desired heat setting 3 
degrees above the current temperature.  Auxiliary heat should come on.  After a few minutes, set the 
mode to "EM Heat".  The heat pump should stop but the auxiliary heat should remain on.  Set the mode to 
“Off”.  Ensure that both the heat pump and auxiliary heat go off. 

7.

 

Set the Mode to "Cool".  Lower the desired cool setting below the current temperature.

  

Ensure that the 

heat pump comes on, in cooling mode.  Set the mode to "Off".  Ensure that the cooling unit goes off. 

8.

 

Press [HOLD] and select “Off” to enable Energy Efficient Control. 

 

Содержание RC-1000

Страница 1: ...s must be observed for installation in Europe CE 1 This equipment must be installed in accordance with National wiring rules for the country in which it is installed 2 All product labels instructions...

Страница 2: ...Removing an existing thermostat 1 Disconnect the power to the control transformer 2 Remove the cover to the existing thermostat 3 Disconnect the wires going to each terminal on the thermostat Label ea...

Страница 3: ...iagram for the application See Figures 8 11 Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the hole with the supplied insulating foam to ensure an accur...

Страница 4: ...must remain in place Figure 4 Thermostat power up for test or configuration purposes Important Notes 1 For HVAC systems with a single transformer for heating and cooling the metal jumper between Term...

Страница 5: ...onfiguration steps under the wiring diagram for the respective HVAC system type 7 If the thermostat or HVAC system does not perform as stated in the Power Up steps under the wiring diagram for the res...

Страница 6: ...res or wire strands at the connections 2 Connect power to the transformer and system The display will show the current thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN...

Страница 7: ...re A temperature sensor can be physically connected to the Remote Temp Sensor terminals on the thermostat or the RC 1000 can obtain the outdoor temperature from a remote system If the RC 1000 can not...

Страница 8: ...d system The display will show all of the thermostat settings 3 Press FAN and select On The fan should come on 4 Press FAN and select Auto The fan should go off 5 Press HOLD and select On to override...

Страница 9: ...m schedules SETTING THE COMMUNICATIONS JUMPER This thermostat comes from the factory with the communications jumper J8 labeled COMM JUMPER on the thermostat printed circuit board installed See Figure...

Страница 10: ...ound Zone 16 and Output 8 See Figure 9 THERMOSTAT CONTROLLER Black Green Yellow UP Communication Jumper Figure 9 Connections to HAI Home Control System Notes 1 Additional thermostats are connected in...

Страница 11: ...Comm on the right terminal strip See Figure 10 UP Green Black THERMOSTAT ANY SYSTEM WITH A RELAY OR 5 15 VDC OUTPUT 5 15 VDC Communication Jumper Figure 10 Connections to a Remote Setback Switch Notes...

Страница 12: ...ed pair with foam polyethylene insulated conductors shielded must be used Wire runs must not exceed 250 feet Make the connections to the Green and Black terminals under the section marked Remote Temp...

Страница 13: ...ns and Scroll Wheel 1 Remove the thermostat face from the thermostat base 2 Remove the local control jumper See Figure 12 3 Align the tabs of the thermostat face with the slots of the thermostat base...

Страница 14: ...gs 6 Read the warning and then press Continue to proceed 7 To exit Setup mode press Back several times until the Home Page is displayed Notes 1 The thermostat will automatically default to the Home Pa...

Страница 15: ...e method for scheduling temperature change commands Program Mode Schedule Program setpoints are based on time of day and day of week None The internal program schedule is disabled Use this when connec...

Страница 16: ...ng again Raising this number will increase the total time that the heating system is off saving energy but may allow the temperature to drift farther from the setpoint decreasing comfort When combined...

Страница 17: ...ance of the HVAC system the anticipator settings are automatic by default However the anticipator settings may be adjusted if desired Heat Anticipator This adjusts the tendency of the thermostat to tu...

Страница 18: ...ry heat is used in a dual fuel heat pump system If the outdoor temperature is above the Upper Balance Setpoint 45 F by default the heat pump is used exclusively If the outdoor temperature falls below...

Страница 19: ...hermostat and the remote system are set to the proper configurations for communication SYMPTOM ACTION TO TAKE Temperature Reading Incorrect 1 Allow 30 minutes for thermostat to adjust 2 Adjust calibra...

Страница 20: ...medies thereof In no event shall HAI be liable for incidental expenses or consequential loss or damages For the complete HAI Warranty for USA policy see the HAI web site at www homeauto com Any implie...

Отзывы: