POWER UP  
 

1.

 

Double check wiring, be sure that there are no stray wires or wire strands at the connections. 

2.

 

It is not necessary to connect the remote system (COMM) cable at this time. 

3.

 

Connect power to the transformer and system.  The display will show all segments for about 5 seconds. 

4.

 

Press the Fan key.  The fan should come on.  Press the Fan key again. The fan should go off. 

5.

 

Set the Mode to "HEAT".  Use the up arrow key to raise the heat setting 1 degree above the current 
temperature.  Stage 1 should start in heating mode.  Raise the setpoint several degrees above the current 
temperature.  Both stages should come on.  After a few minutes, set the mode to "EM HEAT".  The heat 
pump should stop and the auxiliary heating should come on.  Set the mode to OFF.  Ensure that both the 
heat pump and auxiliary heat go off. 

6.

 

Set the Mode to "COOL".  Use the down arrow key to lower the cool setting 1 degree below the current 
temperature.  Stage 1 should start in cooling mode.  Lower the setpoint several degrees below the current 
temperature.  Both stages should come on.  Set the mode to "OFF".  Ensure that the cooling unit goes off. 

 
Note:
 As a convenience to the installer, the compressor start up protection delay can be canceled.  To cancel the 
delay, press the Prog key 3 times, then press the Fan key 2 times.  If the thermostat or system does not perform 
as stated above, recheck all wiring - See Troubleshooting Tips
 
INSTALLER SETUP 
 
This section describes the items that the installer must setup as part of the thermostat installation.  The Installer 
Setup mode is used to configure the general operating parameters of the thermostat. 
 
When in Installer Setup mode: 
 

1.

 

The small digits on the top of the display are the item number.   

2.

 

The large blinking digits in the center of the display are the value of the item number.   

3.

 

Press the Prog (

>

) key to advance to the next item.   

4.

 

Press the Hold (

<

) key to return to the previous item.   

5.

 

Use the arrow keys (

∧−∨

)

 

to change the value of each item.   

6.

 

Do not set the values to anything other than the specified range for each item.   

7.

 

To exit Setup mode, press the Fan key. 

 

The thermostat will automatically exit Setup mode after 20 seconds of no key activity. 

 

To enter the Installer Setup mode, press the Prog key three times (day will flash), then press the Fan key. 
 

 

 
The word "default" indicates the initial setting when the thermostat is delivered from the factory. 

Содержание OMNISTAT RC-112

Страница 1: ...m current 2 A on any circuit 3 A total Thermostat operating current less than 15 mA The following requirements must be observed for installation in Europe CE 1 This equipment must be installed in acco...

Страница 2: ...sting thermostat 3 Disconnect the wires going to each terminal on the thermostat Label each wire with the letter or number at the terminal 4 Remove the existing plate or base from the wall MOUNTING Wh...

Страница 3: ...ation See Figures 7 8 Insert the cable into the connector on the thermostat circuit board marked COMM Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the...

Страница 4: ...s energized for cooling B Terminal is energized for heating In most applications the reversing valve is energized for cooling and should be connected to the O terminal If the heat pump requires the re...

Страница 5: ...5 5 Figure 5...

Страница 6: ...2 To configure the display backlight to always be on set the JP2 Select Backlight Mode jumper to the ON position between the middle and bottom pin on the connector See Figure 6 3 To configure the dis...

Страница 7: ...at the cooling unit goes off Note As a convenience to the installer the compressor start up protection delay can be canceled To cancel the delay press the Prog key 3 times then press the Fan key 2 tim...

Страница 8: ...ured with the following system options WITH NO EEC EEC 0 8 Auto changeover no fan with heat 1 9 Auto changeover fan on with heat 4 12 Manual changeover no fan with heat 5 13 Manual changeover fan on w...

Страница 9: ...isplays add 16 to each value The default setting is 1 04 Calibration offset This item is used to raise or lower the current temperature reading by 1 degree Fahrenheit or 1 2 degree Celsius If this ite...

Страница 10: ...nimum time set by this item When the cooling system turns off it must remain off for a minimum time set by this item Setting Cycles per hour maximum 5 6 6 5 7 4 8 3 7 10 3 The recommended setting is 8...

Страница 11: ...system operation before this reminder is displayed Days Counting down from 10 0 The filter reminder can be disabled by setting this item to 60 16 System runtime This week This item logs the amount of...

Страница 12: ...This thermostat has been preprogrammed with energy saving settings recommended under the EPA Energy Star program When used with remote systems HAI recommends that the thermostat be configured as non p...

Страница 13: ...TCHES The thermostat can be connected to a remote system or remote switch A signal can be sent from the remote location to change the thermostat temperature settings from the DAY setting to the NIGHT...

Страница 14: ...piece of tape Figure 8 Hookup to remote Day Night setback switch OTHER SYSTEMS For connections to personal computers utility management systems and other automation systems refer to connection diagra...

Страница 15: ...at keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check COMM connector and wiring 2 Check thermostat address setting 3 Check communications mode setting Control By Remote System Not Working 4 Ch...

Страница 16: ...Reversing valve is connected to wrong terminal move wire from B to O or from O to B The wires connecting the reversing valve may be reversed See Note 2 Page 4 SYMPTOM ACTION TO TAKE No Auxiliary OR Em...

Отзывы: