TROUBLESHOOTING TIPS 
 

 
 
 

SYMPTOM 

ACTION TO TAKE 

1.

 

Check power to the thermostat 

2.

 

Check wiring diagrams 

Thermostat Dead 

3.

 

Check thermostat temperature sensor 

Thermostat will not operate with a damaged temperature sensor 

 

SYMPTOM 

ACTION TO TAKE 

1.

 

Check for break in G, W, or Y wire 

2.

 

Allow minimum off time to pass 

3.

 

Check system options for correct settings 

Fan, Heat, Or Cool 
Inoperative 

4.

 

Remote system is overriding thermostat 

"REMOTE"

 is displayed when system is overriding thermostat.  Disconnect the cable from 

"COMM" connector to test 

SYMPTOM 

ACTION TO TAKE 

1.

 

Mode is Off  (Select Heat, Cool, or Auto) 

Can't Adjust Temperature 

2.

 

Check if thermostat keys are disabled 

To enable thermostat keys for test, remove jumper 

 

SYMPTOM 

ACTION TO TAKE 

  1.  Check COMM connector and wiring 
  2.  Check thermostat address setting 
  3. 

Check communications mode setting 

Control By Remote System 
Not Working 

  4.  Check setup of the remote system 

Ensure that all setup items for the thermostat and the remote system are set to the proper 

configurations for communication 

 

SYMPTOM 

ACTION TO TAKE 

1.

 

Allow 30 minutes for thermostat to adjust to room 

temperature 

2.

 

Adjust calibration offset 

Temperature Reading 
Incorrect 

3.

 

Change setup option to display 

o

F or 

o

After installation, allow the thermostat up to 30 minutes for an accurate temperature reading 

 

SYMPTOM 

ACTION TO TAKE 

Display Problem 

1.

 

Disconnect power to the thermostat.  Reconnect, then 

observe display self-test 

 

For a 5 second period after power is reconnected, all segments of the display should light indicating 

all thermostat functions 

 

Содержание OMNISTAT RC-112

Страница 1: ...m current 2 A on any circuit 3 A total Thermostat operating current less than 15 mA The following requirements must be observed for installation in Europe CE 1 This equipment must be installed in acco...

Страница 2: ...sting thermostat 3 Disconnect the wires going to each terminal on the thermostat Label each wire with the letter or number at the terminal 4 Remove the existing plate or base from the wall MOUNTING Wh...

Страница 3: ...ation See Figures 7 8 Insert the cable into the connector on the thermostat circuit board marked COMM Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the...

Страница 4: ...s energized for cooling B Terminal is energized for heating In most applications the reversing valve is energized for cooling and should be connected to the O terminal If the heat pump requires the re...

Страница 5: ...5 5 Figure 5...

Страница 6: ...2 To configure the display backlight to always be on set the JP2 Select Backlight Mode jumper to the ON position between the middle and bottom pin on the connector See Figure 6 3 To configure the dis...

Страница 7: ...at the cooling unit goes off Note As a convenience to the installer the compressor start up protection delay can be canceled To cancel the delay press the Prog key 3 times then press the Fan key 2 tim...

Страница 8: ...ured with the following system options WITH NO EEC EEC 0 8 Auto changeover no fan with heat 1 9 Auto changeover fan on with heat 4 12 Manual changeover no fan with heat 5 13 Manual changeover fan on w...

Страница 9: ...isplays add 16 to each value The default setting is 1 04 Calibration offset This item is used to raise or lower the current temperature reading by 1 degree Fahrenheit or 1 2 degree Celsius If this ite...

Страница 10: ...nimum time set by this item When the cooling system turns off it must remain off for a minimum time set by this item Setting Cycles per hour maximum 5 6 6 5 7 4 8 3 7 10 3 The recommended setting is 8...

Страница 11: ...system operation before this reminder is displayed Days Counting down from 10 0 The filter reminder can be disabled by setting this item to 60 16 System runtime This week This item logs the amount of...

Страница 12: ...This thermostat has been preprogrammed with energy saving settings recommended under the EPA Energy Star program When used with remote systems HAI recommends that the thermostat be configured as non p...

Страница 13: ...TCHES The thermostat can be connected to a remote system or remote switch A signal can be sent from the remote location to change the thermostat temperature settings from the DAY setting to the NIGHT...

Страница 14: ...piece of tape Figure 8 Hookup to remote Day Night setback switch OTHER SYSTEMS For connections to personal computers utility management systems and other automation systems refer to connection diagra...

Страница 15: ...at keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check COMM connector and wiring 2 Check thermostat address setting 3 Check communications mode setting Control By Remote System Not Working 4 Ch...

Страница 16: ...Reversing valve is connected to wrong terminal move wire from B to O or from O to B The wires connecting the reversing valve may be reversed See Note 2 Page 4 SYMPTOM ACTION TO TAKE No Auxiliary OR Em...

Отзывы: