The following table recapitulates the interpretation of each LED
LED function
LED ref
Status
Description
Power
Off
Unit without power
Blinks green
Unit start-up phase
Lights up green
Unit started
Blinks red
Unit supplied by the power reserve (10 s
max)
Lights up red
OS loading error
KNX
Off
Unit supplied by the power reserve (10 s
max)
Blinks green
Connected to the KNX bus - bus traffic
Lights up green
Connected to the KNX bus
– no bus traffic
Lights up red
No KNX bus connection
Ethernet 1 and
2
et
Off
No network (or operating on power reserve
–
10 s max)
Blinks green
No DHCP server detected, operating on
fallback IP address
Lights up green
Network detected and IP address allocated
Lights up red
IP address conflict
Blinks red
Waiting for IP address allocation
Portal
Off
No Hager portal connection
Blinks green
Hager portal connection attempt
Lights up green
Hager portal connection established
Lights up red
Hager portal connection inaccessible or
connection refused
Bus voltage
present
Lights up red
Check the bus voltage with a short press of
button
. Red LED lit indicates KNX bus
present.
SOFTWARE VERSION UPDATE FOR THE CONFIGUARATION SERVER
2.4
It is mandatory to update the IoT Controller software version before any first use.
The update is carried out
Automatically
when the IoT Controller is connected to an Internet box.
Connection to the network and the remote server is made automatically for the update (see chapter
5.8.7
for
configuration of the automatic update).