Alarms menu
7.3 Submenu contents
NOTE
The measurement attributes within the Custom submenu depend on the protection
settings defi ned in the Energy MCCB (3P/4P, Ground fault activation, Neutral
activation...). Therefore not all combinations of the listed parameters are always
possible.
Type of Measurement
Option 1 (measurement attribute)
Option 2 (alarm activation condition
on Option 1)
Current
I1, I2, I3, IN, IMax, I1Unb, I2Unb,
I3Unb, IMaxUnb, IAvg
Over, Under
Ground
-
Over, Under
Voltage
V1, V2, V3, VN, VMax, VMin, V1Unb,
V2Unb, V3Unb, VMaxUnb, Vavg, U12,
U23, U31, Umax, Umin, U12Unb,
U23Unb, U31Unb, UmaxUnb
Over, Under
Power
Pd1, Pd2, Pd3, PdTot, Pr1, Pr2, Pr3,
PrTot; Qd1, Qd2, Qd3, QdTot, Qr1,
Qr2, Qr3, QrTot, S1, S2, S3, Stot
Over, Under
Pow. Fact.
PF1, PF2, PF3, PF tot, cosφ1, cosφ2,
cosφ3, cosφTot
Lagging, Leading
THD
I1, I2, I3, V1, V2, V3, U12, U23, U31
Over
Frequency
-
Over, Under
Demand
I1, I2, I3, IN, IAvg, P, Q, S
Over, Under
Quadrant
Quadrant 1, Quadrant 2, Quadrant 3,
Quadrant 4
-
Phase seq.
1, 2, 3 ; 1, 3, 2
-
Lead or Lag
Lead ; Lag
-
NOTE
If a custom alarm is defi ned and set to None priority, the alarm is created but remains
deactivated as long as its priority is set to None.
For more explanations on measurement settings refer to the h3+ Communication
system manual (see Related documents on page 10).
Parameter
Unit
Description
Threshold Ir
% Ir
60 to 95; default 90, set in steps of 5.
Delay
% tr
5 to 80; default 50, set in steps of 5.
Parameter
Description
Long
Set alarm priority for Long-time tripping; default High.
Short
Set alarm priority for Short-time tripping; default High.
Instantaneous
Set alarm priority for Instantaneous tripping; default High.
Ground
Set alarm priority for Ground tripping; default High.
Trip Test
Set alarm priority for the trip test with the h3+ Confi guration tool; default High.
Parameter
Description
Assignment
Default Pre-trip Alarm; Assign an alarm* to OAC output contact.
Reset mode
Latching / Automatic; Set behaviour of OAC contact; Latching:
acknowledgment required through Modbus to set OAC contact back to normal
position; Automatic: no acknowledgement required; default Automatic.
(*) List of alarms that can be assigned to the OAC output contact.