DIP SWITCH SETTINGS

REQUEST TO EXIT PERIOD 

– The Request to Exit (REX) time is selectable for 1, 15, 20, or 30 seconds.  The REX time is 

the period of time the lock will remain “bypassed”, after a remote normally open contact switch is momentarily activated.  

When activated with an access control system, the REX time cycle begins immediately after the access control open time 

expires.  The 2958 will automatically relock if the door is opened, and then closed during the REX time cycle.  

TRIGGER TYPE

 – The trigger type is selectable for “REMOTE” or “INTERNAL”.  Selecting INTERNAL mode uses the internal 

trigger sensor to activate the Exit Delay cycle.  Selecting REMOTE mode disables the internal trigger.  Activation of the Exit 

Delay cycle is triggered by an external exit device equipped with a normally open contact switch.

POWER-UP OPTION*

 – The power-up option, indicating the state of the 2958 upon restoration of system power, is 

selectable to “UNLOCKED” or “LOCKED”.  In the LOCKED mode, the 2958 will attempt to reset to secure mode.  In the 

UNLOCKED mode, the 2958

 

will remain unlocked and the digital display will indicate two horizontal bars “--“.  Turning the 

reset switch momentarily to the reset position will relock and rearm the door.  This feature enables the 2958

 

to comply with 

code requirements in jurisdictions that require manual reset/relock upon loss and restoration of system power.

ALARM TYPE

 – The alarm type is selectable to “TONE ONLY” or “VOICE”.  When secure, the 2958 digital display will 

indicate a 15 second delay time.  Upon activation of the irreversible Exit Delay cycle, the digital display begins counting 

down to zero.  In VOICE mode, the countdown will be accompanied by a warning beeping tone and verbal exit instructions.  

When the digital display indicates zero, the 2958

 

releases.  The speaker output changes to a continuous warning tone and 

the verbal instruction announces “Exit Now”.  In TONE ONLY mode, the countdown will be accompanied by a warning 

beeping tone only, which changes to a continuous tone once the Exit Delay cycle expires.

MESSAGE TYPE

 – The message type is selectable to “MSG1” or “MSG2”.  

MSG1:  (Female Voice) “Exit in 12 seconds, facility staff has been notified...Exit in 5 seconds...exit now...”

MSG2:  (Male Voice) “Exit in 12 seconds, security has been alerted...Exit in 5 seconds...exit now…”

Both messages repeat “Exit now” until the lock is reset. 

WARNING!

CONTACT AUTHORITY HAVING 

JURISDICTION    FOR APPROVAL    

PRIOR TO SELECTING DELAY TIME 

OR PWR-UP SETTINGS

*

OFF

MESSAGE TYPE

VOICE / TONE

PWR-UP 

OPTION*

REQUEST TO EXIT

RELOCK DELAY 

(SEC)

NUISANCE 

DELAY*

2

0

1

5

3

0

1

UNLOCKED

TONE 

ONLY

MSG 

#2

2

1

7

6

5

4

3

8

ON

TRIGGER TYPE

INTERNAL

O N

NUISANCE DELAY*

 – The Nuisance delay time feature, intended to avoid accidental triggering, is selectable for 1 or 2 seconds.  

Releasing the door latch and pushing on the door will activate the internal trigger sensor.  Activating the trigger beyond the 

nuisance delay time will start the irreversible Exit Delay cycle time.  The Nuisance Delay time period is included in the lock release 

cycle and it will not increase or decrease the “total time to unlock” once the 2958

  

is activated.  Releasing the door before the end 

of the Nuisance delay time will turn off the warning alarm and reset the 2958 to secure mode.

RELEASE TIME*

 – The Release time is selectable for 15 or 

30 seconds.  The Nuisance Delay time period is included in 

the door release cycle and it will not increase or decrease the 

“total time to unlock” once the MagLock

  

is activated.  

1 SEC.

2 SEC.

RELEASE

TIME*

15 SEC.

30 SEC.

JUMPER SETTINGS

JUMPER J6

 

(Fire Alarm Input) 

– Factory Installed.  

Remove J6 only if a dry, normally closed contact from a 

fire alarm OR smoke detector system is connected to the 

Fire Panel [FP] terminals.

INSTALLED:

  The 2958 will enter the alarm mode if the 

door is held open past the request to exit period. 

REMOVED:

  The 2958 will remain unlocked if the door is 

held open past the request to exit period.  No alarm will 

sound.  The 2958 will relock and rearm upon closure of the 

door. 

JUMPER J7 (DOOR PROP)

LOCKED

VOICE

MSG 

#1

REMOTE

J7

JUMPER J6

(SEE PG 9)

C  NC

-     +

-     

+

NC 

N

O

N

O  

C

C  

N

C

N

O  

C

N

O  

C

N

O  

C

NO  

C

N

O  

C

NC 

NO

C  

NC

[    

BAS    

]

[    

DPS    

]

[RES

ET]

[RM 

TRIG]

[REX

]

[RED 

RLY]

[GRN RLY]

[ LOCK 

]

[  FP  

]

[  PWR  ]

J6

J

7

J

2

[IBO

]

[EXT 

SPKR]

2958 Delayed Egress MagLock

Installation Instructions

S-EA00051

3/28/12

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 ● (800) 325-9995

9

Содержание 2958 Delayed Egress MagLock

Страница 1: ...peration complies with BOCA National Building Code and the Chicago Building Code UL Listed Special Locking Arrangements and Auxiliary Locks The releasing operation of the 2958 is the same as described above with the exception that the door relocks automatically 30 seconds after closure Each time the door is open before 30 seconds has elapsed the relock timer resets and relocks the door in 30 secon...

Страница 2: ...TED LINE Mark location five places 10 self dril tap screws provided for up to 1 8 thick metal applications Note Machine screws provided for applications with heavier gauge material Drill 21 and tap for 10 32 screw PLACE AGAINST LOCK JAMB FOR L H DOORS 1 4 DIA GUIDE PIN HOLE 9 16 DEEP PLACE AGAINST LOCK JAMB FOR R H DOORS PLACE AGAINST DOOR Center punch on mark 2958 Delayed Egress MagLock Installat...

Страница 3: ...MAKE PROPER ADJUSTMENTS OF THE LOCK S POSITION PRIOR TO MARKING DRILLING AND TAPPING THE FOUR PERMANENT MOUNTING PLATE HOLES 1 2 DIA FOR WIRE First install mounting plate at two slot locations only and make proper adjustments before marking remaining five mounting hole locations FOLD ON DOTED LINE Mark location five places 10 self dril tap screws provided for up to 1 8 thick metal applications Not...

Страница 4: ...ting screws using a soft hammer to avoid damage to the lock case ARMATURE MOUNTING INSTRUCTIONS Figure 2B HOLLOW METAL DOOR From sexnut side of door drill exactly 1 2 hole through one metal thickness only From armature side of door drill 5 8 hole to insert reinforcement tube Press in sexnut reinforcement tube all the way and mount armature to door using hardware provided per Figure 2B Figure 2A SO...

Страница 5: ...TECTION SYSTEM IS CONNECTED TO FP INPUT Pg 8 3 or 5 conductors 8 or 10 conductors Power Supply To Fire Panel AC Mains 2 conductors PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS Key Switch or Access Control Optional To Smoke Detection System 2 conductors Digital Keypad 2958 Delayed Egress MagLock Installation Instructions S EA00051 2900 Series Power Supply Key Switch Reset Station Remote Speaker...

Страница 6: ...rs Model 2958T REMOVE J6 ONLY IF A FIRE PANEL OR SMOKE DETECTION SYSTEM IS CONNECTED TO FP INPUT Pg 8 SLAVE To Smoke Detection System 2 conductors TB2 TB1 LOCK IN PWR TB5 TB6 TB4 TB3 DPS BAS TB7 NO C NC NO C NC NO C NC NO C Z4 D1 Z1 D2 R7 RLY1 J1 R9 C4 BAS DPS C1 J4 TB8 ATS TRIG OUT C NC NC NO NO C C NC NO C NO C NO C NO C NO C NC NO C NC BAS DPS RESET RM TRIG REX RED RLY GRN RLY LOCK FP PWR J6 J7...

Страница 7: ... 2 Whenever the IBO input is closed and held the 2958 will instantly relock and rearm Egress is possible as the normal 15 30 sec delayed unlock 3 Releasing the IBO input will return the 2958 to the Bypass mode 4 Releasing the REX input will rearm the system 5 Upon power up you must manually reset the lock to activate the IBO input System Operation OPTIONAL RED GRN BLK WHT BLK BLU RED L3 OPTI ON C ...

Страница 8: ... GRN RLY RED RLY RM TRIG RESET REX 12 VDC OR 24 VDC TO CLOSED FIRE SMOKE DETECTOR CONTACT SLAVE TANDEM LOCK POWER TERMINALS LOCK SECURE OUTPUT ALARM OUTPUT EXTERNAL TRIGGER SWITCH INPUT EXTERNAL RESET SWITCH INPUT REQUEST TO EXIT INPUT IBO INSTANT BYPASS OVERRIDE INPUT N O COM JUMPER J6 SEE PG 9 C NC NC NO NO C C NC NO C NO C NO C NO C NO C NC NOC NC BAS DPS RESET RM TRIG REX RED RLY GRN RLY LOCK ...

Страница 9: ...ype is selectable to MSG1 or MSG2 MSG1 Female Voice Exit in 12 seconds facility staff has been notified Exit in 5 seconds exit now MSG2 Male Voice Exit in 12 seconds security has been alerted Exit in 5 seconds exit now Both messages repeat Exit now until the lock is reset WARNING CONTACT AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO SELECTING DELAY TIME OR PWR UP SETTINGS OFF MESSAGE TYPE VO...

Страница 10: ...se the door and apply power to the lock The digital display will show a two bars indicating that the lock is in the Manual Power Up mode Push on the door to verify that the door is unlocked Reset the lock at this time by turning the built in key switch clockwise or by triggering the remote reset input The lock should now secure the door and the LED display will show the delay time You may change t...

Страница 11: ...ptional Alarm Output Lock Status Relay Output Door Secure Door Unlocked Specifications Interior Applications Only Input Voltage Requirements Dual Voltage Auto Sensing 12 24 VDC 10 Use with a UL 294 Standard Power Supply Power Consumption Standard Model 1650 lbs 2958 820 500 mA 12 24 VDC 2958T 1500 850 mA 12 24 VDC Energy Saver 1200 lbs E Option 2958 452 274 mA 12 24 VDC 2958T 660 686 mA 12 24 VDC ...

Страница 12: ...CONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS Systems Applications Reference Activation by a remote trigger for doors with or without latching hardware Activation by applying pressure to doors with latching hardware 2958 Delayed Egress MagLock ...

Отзывы: