Standard Features
1650 lbs. Holding Force
15 or 30 Second Exit Delay when activated.
1 or 2 Second Nuisance Delay
75dB Alarm Tone with Digital Display & Selectable
Voice Instruction
Choice of Activation Trigger:
- Door Movement
- Exit Device w/ REX Switch
- Touch Sense Bar w/REX Switch
Vandal resistant Proximity Sensor Trigger
Auto Sensing 12/24VDC input power
Connection for Tandem Option (Pairs of Doors)
Optional Features
DPS
Door Position Switch
MBS
Bond Alert Sensor
ATS
Anti Tamper Switch
Selectable Automatic & Manual Power-Up
Feature
Auto Power-Up – Occurs when power is restored
and/or the fire panel is restored.
Manual Power-Up –
This is a UBC & California
Building Code Compliant Feature –
Only after power
restoration and fire panel reset may the lock be reset
manually at the opening. Lock can be reset with the
built-in reset key switch or, a key switch or keypad
adjacent to the door.
Inputs & Outputs
REX Input
Fire Alarm/Smoke Detection System Release
Remote Reset Input
Remote Trigger Input
Tandem/Slave Lock Input
IBO – Instant Bypass Override
DPS – Door Position Status (Optional)
MBS – Magnetic Bond Status (Optional)
ATS – Anti-Tamper (Optional)
Alarm Output
Lock Status Relay Output
- Door Secure
- Door Unlocked
Specifications
Interior Applications Only
Input Voltage Requirements:
Dual Voltage (Auto Sensing) –
12/24 VDC (+/- 10%)
(Use with a UL 294 Standard Power Supply)
Power Consumption:
Standard Model (1650 lbs.) -
2958 – 820/500 mA@ 12/24 VDC
2958T – 1500/850 mA @ 12/24 VDC
Energy Saver (1200 lbs., “E” Option) –
2958 – 452/274 mA@ 12/24 VDC
2958T – 660/686 mA @ 12/24 VDC
Size: 11"L x 2-3/4"H x 2-5/8"D
Lock Status Relay Rating: 1 Amp @ 30V resistive
Alarm Output Rating: 1 Amp @ 30V resistive
DPS Rating: 250 mA @ 30V resistive
BAS Rating: 250 mA @ 30V resistive
ATS Rating: 1 Amp @ 30V resistive
Operating Condition: 0-49 deg C, 85% RH
(non-condensing)
Building & Fire Life Safety Code Compliant
2958ND
IBC
International Building Code
IFC
International Fire Code
NFPA 101
Life Safety Code
NFPA 1, UFC
, Uniform Fire Code
UBC
Uniform Building Code
CBC
California Building Code
SBC
Standard Building Code
2958BD
BOCA
National Building Code compliant
Chicago
Building Code compliant
GWXT, GWXT7 - Auxiliary Locks - UL,cUL Listed
FWAX - Special Locking Arrangements - UL Listed
Only the 2958 and the 2958T have
been UL listed as Special Locking
Arrangements to UL Standard 294,
and NFPA 101.
2958 Delayed Egress MagLock
Installation Instructions
S-EA00051
3/28/12
HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 ● (800) 325-9995
11