To protect against the spread of both fire and fire gas, the  
damper must be controlled by a smoke detector mounted in 
the ventilation duct near the damper or in another suitable  
location and be equipped as specified below. 

To protect against the spread of fire alone, the damper must 
be controlled by a smoke and/or heat detector mounted in 
the ventilation duct near the damper or in another suitable 
location. 

The heat detector must close the damper at a temperature  
of no more than +72 degrees in the duct.

CONTROL

The fire gas damper must be function tested at least once 
every 48 hours. The function test means that the dampers 
must close and open at intervals as above. 

The function test must be performed automatically and can  
be controlled by e.g. a control and monitoring system.

MONITORING

At the function test interval, the damper’s closing function  
is checked automatically. If any damper does not close, a  
malfunction should be indicated immediately. 

OPERATING AND MAINTENANCE INSTRUC-

TIONS

Periodic inspection once per year.

INTERNAL CONTROL VIA INSPECTION COVER 
OR CLEANOUT DOOR IN CONNECTING DUCT

– Check by triggering the smoke detector so the  
  damper closes.

– Check that the damper blade closes and opens freely by  
  switching off power to the actuator. If the junction box  
  KBHA-1 is installed, press the “DAMPER TEST” button. 
  Keep the button pressed to interrupt the voltage to the  
  actuator. Alternatively, the voltage can be interrupted by  
  pressing the “Test” button on the damper’s thermal sensor.

– Check the fitting of the sealing strip on the damper blade.

– Check the cleaning requirements in conjunction with the  
  ventilation system function test.

EXTERNAL CONTROL

– Check that the damper frame has not been  
  subjected to mechanical damage.

– Check that the seal in the structural element has 
  not been damaged.

– Check the fitting of the actuator on the shaft and frame.

– Check that the actuator cabling is not damaged.

– Check that the damper is clean. If necessary, wipe with  
  a slightly dampened cloth.

CLEANING 

– When cleaning the inside of the damper, always choose  
  a gentle cleaning method such as a nylon brush and/or  
  compressed air.

SPARE PARTS LIST

 

Actuator brand Gruner or Belimo, see rating plate on  
the actuator.

HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

Flodin Fernstr

öm  |  01  2019

INTACT

 

Fire/Fire gas damper

Hagab

  Box 135, 56202 Taberg  

|

  

Visit

 Industrivägen 5, 56241 Taberg  

|

  

Phone

 036-363090  

|

  Fax

 036-363099

[email protected]  

|

  www.hagab.com  

|

  

Sales Office

 

Jönköping 

Phone

 036-363090  

|

  Stockholm 

Phone

 08-6899010

Drawing name:

Отзывы: