HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

3. Installation 

Install the damper in the ventilation duct. The shaft of the 
damper can be installed in any position. Fix with plate 
screws. Suspension devices for INTACT must match the fire 
resistance rating of the structural element. See for example 
the Svensk Ventilation/HVAC Technical Association’s manual 
“Practical solutions for fire protection and ventilation”.

4. No connection in the duct system 

If the fire/fire gas damper is not connected to  
the duct system, e.g. when installing as a closing device or 
transfer air device, the damper must be fitted with contact 
grilles on the non-connected side. The minimum permissi-
ble distance between the damper  
blade in the open position and the grille is 50 mm.

6. Insulation 

Insulate the duct to an approved method according  
to the insulation supplier’s instructions. 

Note that the insulation must cover the whole  
INTACT damper.

5.

6.

D + 50 mm

ev. 4.

3.

5. Thermal sensor

 

Install the thermal sensor with the sensing unit in the air flow 
without hindering damper blade movement. 

Drawing name: