HAGAB – INSTALLATION, OPERATION AND MAINTENANCE

4. Opposite side of the duct 

Install the duct on the other side of the structural element 
and fix it to the damper fitting with plate screws.

5. Suspension devices 

Suspension devices for the damper must match the fire 
resistance rating of the structural element. See for example 
the Svensk Ventilation/HVAC Technical Association’s manual 
“Practical solutions for fire protection and ventilation”.

6. Lead-though/Sealant 

The space between the installation sleeve and connecting 
duct can be fitted with fireproof insulation made of mineral 
wool or an equivalent sealant.

DAMPER INSTALLATION – CONCRETE JOISTS

1. Installation 

Install the ventilation duct mounted to the damper  
according to the same principle as for a vertical structural 
element but without an installation sleeve.  

Centre the damper and fix to the top of the joists 

with 

the supplied L brackets. Refinish the space between the 
ventilation duct and the joists with concrete mortar or a 
certified fire protection compound.

INTACT

 

Fire/Fire gas damper

Refinishing

The damper is  
installed on the  
top of the joists

Drawing name: