SERVICE & MAINTENANCE

Your Fire Alarm System is working 24 hours a day, 365 days a year. The detectors and control & indicating 
panel are operating continuously and the fire alarm circuits are constantly monitored. 

Legislation such as the Regulatory Reform (Fire Safety) Order 2005 and other legislation protecting both 
employees and the public require premises operators to conform with standards for Fire Alarm Systems.

It is a requirement of BS 5839 Part 1 that the system is subject to periodic inspection and servicing so that 
faults are identified, preventive measures can be taken to ensure the continued reliability of the system,  
false alarm problems are identified and suitably addressed, and the user is made aware of any changes to 

the building that affect the protection afforded by the system.

The inspection and servicing recommendations in this clause should be carried out by a competent 

person. A ‘Competent Person’ is a person or fire alarm servicing organisation with specialist knowledge 
of  fire  detection  and  fire  alarm  systems,  including  knowledge  of  the  causes  of  false  alarms,  sufficient 

information regarding the system, and adequate access to spares.

The period between successive inspection and servicing visits should be based upon a risk assessment, 
taking into account the type of system installed, the environment in which it operates and other factors 
that may affect the long term operation of the system. The recommended period between successive 

inspection and servicing visits should not exceed six months. If this recommendation is not implemented, 
it should be considered that the system is no longer compliant with this part of BS 5839

THE NEED FOR MAINTENANCE

ROUTINE MAINTENANCE & TESTING

DUTIES OF THE RESPONSIBLE PERSON

The system user needs to appoint a single, named member of the premises management to supervise 

all matters pertaining to the fire detection and fire alarm system. The role of this person is to ensure that 
the system is tested and maintained in accordance with the recommendations of  BS 5839 Part 1, that 

appropriate records are kept and that relevant occupants in the protected premises are aware of their roles 

and responsibilities in connection with the fire detection and fire alarm system.

This person also needs to ensure that necessary steps are taken to avoid situations that are detrimental to 
the standard of protection afforded by the system and to ensure that the level of false alarms is minimized.

DAILY

The ‘Responsible Person’ should check the control panel to make sure no faults or pre-alarm conditions 
are indicated and that the green ‘Supply Healthy’ lamp is lit.

WEEKLY

The Fire Alarm System should be tested on a weekly basis as recommended in BS5839 Part 1 clause 44.2.

Every week a manual call point should be operated during normal working hours. The weekly test should 
be carried out at approximately the same time each week. Instructions to the occupants should be that 
they report any instance of poor audibility of the fire alarm signal.

A different manual call point should be used at the time of every weekly test so that all manual call points 

in the building are tested in rotation over a prolonged period.

The result of the weekly test and the identity or location of the manual call point used should be recorded 
in the system log book.

The following section is a summary of the requirements in BS5839 Part 1

For comprehensive information a copy of BS5839 Part 1 can be purchased from the British Standards 
Institution via their web site at www.bsi-global.com.

Содержание Esento Eclipse ECL-2

Страница 1: ...Installation Commissioning Operating Manual EN54 APPROVED 2 4 ZONE CONVENTIONAL CONTROL PANEL Approved Document UI ECL 01 Issue 8 0 810a 03 ...

Страница 2: ...responsibility of the This fire alarm system requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order system user to ensure it is regularly serviced and maintained in good working order Disclaimer Disclaimer No responsibility can be accepted by the manufacturer or distributors of this...

Страница 3: ...C 11 INSTALLATION 12 SAFETY 12 ESD PRECAUTIONS 13 GENERAL 13 MOUNTING THE CABINET 13 MAINS CONNECTIONS 14 CONNECTING THE BATTERIES 15 SETUP PROGRAMMING 16 TWIN WIRE MODE 16 LEVEL 3 ENGINEERING OPTIONS 17 ZONE INTERFACE FUNCTION 25 OPERATING 26 PANEL CONTROLS INDICATIONS 26 DISABLE MODE 28 TEST MODE 29 FAULT DIAGNOSIS 30 FUNCTIONALITY DURING A SYSTEM FAULT 31 USER INSTRUCTIONS 31 SERVICE MAINTENANC...

Страница 4: ...ccess to the function options The three main buttons RESOUND red SILENCE system and allow access to the function options The three main buttons RESOUND red SILENCE blue and RESET green being much larger and colour coded to assist the end users blue and RESET green being much larger and colour coded to assist the end users Two or four fire zone circuits are provided plus two monitored sounder circu...

Страница 5: ...Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 3 ABOUT THIS PANEL CABINET Fire Detection System 57mm 80mm 260mm 308mm 250mm 300mm ...

Страница 6: ...ABOUT THIS PANEL CIRCUIT BOARDS Eclipse panels comprise of two circuit boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 BATTERY 1 2 3 ON 1 2 3 4 ENTER RESOUND SILENCE RESET TPCA01 E2 E4 2 or 4 zone Master PCB TPCA02 LED Display Controls PCB ...

Страница 7: ... 500mA 28v input for power supply Temperature compensation voltage control link Commmon fire VFCO relay unfused Max 3A 30vdc Commmon fault VFCO relay maintained fail safe unfused Max 3A 30vdc Common fire O P Common fault O P Alert pulses sounders Precint class change activates sounders Switched ve inputs Switched ve outputs Max load 40mA To 0 volts Relay Coil Conventional monitored sounder circuit...

Страница 8: ...rent 3 amps Input voltage 22vdc to 32vdc 28v 0v power output 28vdc supply output for fire alarm accessory relays etc Max continuous use 400mA Fused 500mA Fuse 500mA resettable fuse Common fire relay Fire relay contact Clean C O Max 3A 30vdc Unfused Common fault relay Maintained fault relay contact Clean C O Max 3A 30vdc Unfused Outputs FR FLT Switched ve voltage outputs for relay control Overload ...

Страница 9: ...ample 4 Zone I min 85mA 2 Zone I min 75mA Maximum ripple 120 mV p p Supply and charger fault monitored Min max battery size and type 2 x 3 2Ahr 12volt VRLA Use Yuasa NP range batteries Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval Battery charging voltage 27 3 vdc nominal at 20 deg C Temperature compensated Battery charging output current 1 5A PS...

Страница 10: ...giving an actual coverage of 112m2 per device When mounted on a flat ceiling heat detection devices have an individual coverage of 5 3m radius However these radii must overlap to ensure there are no blind spots Therefore individual coverage can be represented by a square measuring 7 5m x 7 5m giving an actual coverage of 56 3m2 per device Call Points A person should not have to travel more than 45...

Страница 11: ...and recommended for use with that cable The screen or drain wire of circuits should be bonded to earth at recommended for use with that cable The screen or drain wire of circuits should be bonded to earth at one location only and should be continuous throughout the circuit Drain wires should be terminated in the one location only and should be continuous throughout the circuit Drain wires should b...

Страница 12: ...ng Typical Conventional Sounder Circuit Wiring 4K7 OHM END OF LINE RESISTOR 4K7 OHM END OF LINE RESISTOR ZONE 1 SNDR1 R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 MANUAL CALL POINT MCP1A R 470 1 2 3 4 _ _ 470 MOTORISED BELL POLARISED MOTORISED BELL POLARISED ELECTRONIC SOUNDER POLARISED ELECTRONIC SOUNDER POLARI...

Страница 13: ...circuit the sounders are connected in reverse polarity to the detectors and call points Note Zone circuit configuration is set to Conventional by default Twin Wire mode must be set using DIL Switch 1 on Main PCB ZONE 1 APOLLO TWIN WIRE BASE 45681 206 APOLLO TWIN WIRE BASE 45681 206 TWIN WIRE CALL POINT MCP1B R TW TWIN WIRE CALL POINT MCP1B R TW 1 2 3 4 _ _ 470 1 2 3 4 _ _ 470 VE VE MOTORISED BELL ...

Страница 14: ...er According to the provisions of the Act you are therefore requested to take such steps as are necessary to According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned ensure that any appropriate information about this product is made available by y...

Страница 15: ...ssed as extra low voltage and must be segregated away from mains voltage Any junction boxes used should be clearly labelled FIRE ALARM Any ancillary devices e g door retaining magnets must be powered from a separate power source Any coils or solenoids used in the system must be suppressed to avoid damage to the control equipment The site chosen for the location of the panel should be clean dry and...

Страница 16: ...ins supply should be brought into the panel via one of the knockouts provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable ring crimp Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block whi...

Страница 17: ... doesn t clear after 1 minute check connections The battery charging voltage is factory calibrated to 27 3vdc 0 2v 20o C This should not normally require adjustment Where battery problems are experienced the following information should be considered a If a battery is disconnected from the charger no voltage will appear on the output leads or terminals due to intelligent battery controls b Check t...

Страница 18: ...nders and beacons need to be wired in opposite polarity to the detectors and call points i e zone positive wire connects to detector base and call point positive terminals but sounder and beacon negative terminals SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 1 2 3 ON 1 2 3 ON 1 2 3 ON 1 2 3 4 5 6 7 Switch in upward position ON To set Twin Wire mode move switch 1 on the 3 way DIL switch located on the main ...

Страница 19: ...R button Then press the ENTER button again and hold for 3 seconds Any disablements or test mode settings will now clear and all engineering option parameters will revert back to factory settings The panel will bleep to acknowledge the reset RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test L...

Страница 20: ...nged It is also possible to disable the use of a code entry to enable controls forcing the use of the key switch only Enter the above code and press the ENTER button The Zone Fault Disabled Test LEDs will start to rapidly pulse in sequence to show the currently set code The sequence will be repeated twice after which time the panel will automatically drop out of the set keypad entry mode Whilst th...

Страница 21: ... ENTER button again will toggle the status indicated by a rapid or slow pulsing LED see below Then use Button 1 to move to the next zone If the zone has been set to not resound alarms the LED will be off If kept as default new fire condition will resound alarms then the LED will be on steady Rapid Pulse Zone is under selection and is set to have alarms resound default Slow Pulse Zone is under sele...

Страница 22: ...the circuit Note Twin Wire mode is not compatible with intrinsically safe operation Detector removal monitoring EN54 The detector removal monitoring can be turned off For use with older non compliant detectors Enter the above code and press the ENTER button The zone 1 fire LED will light This indicates setting the above attributes for zone 1 The amber fault disabled test LEDs will show the current...

Страница 23: ...settingoftheattributeisindicated by the amber fault disabled test LED ON or OFF Use button 2 to switch the attribute ON or OFF indicated by the amber fault disabled test LED Then use button 1 to move to the next attribute if required Press the ENTER button to return back to the zone selection indicated by a steady zone fire LED RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer...

Страница 24: ... A 470Ω call point will be included in the dependency delay sequence By default this is set to off for all zones To set zones to Type A Dependency enter the above code and press the ENTER button The Aux Output Status LED will pulse slowly Zone Fault Disabled Test LEDs will show their current status see below with Zone 1 pulsing to indicate it is under selection Use Button 1 Disable Mode to move to...

Страница 25: ...ith their relevant Sav Wire bases the above compatibility mode must be switched on Enter the code 2 1 3 4 Zone 1 fire LED will pulse Pressing the ENTER button will illuminate zone 1 Enter the code 2 1 3 4 Zone 1 fire LED will pulse Pressing the ENTER button will illuminate zone 1 Fault Disabled Test LED indicating that the compatibility mode is set to on Pressing the ENTER button again will toggle...

Страница 26: ...uent presses will toggle between them With the required fire LED lit press the ENTER button and Zone 1 fire LED will pulse Press button 2 Test Mode to alter the status of the output represented by the Zone 1 Fault Disabled Test LED either off or on Off Output cancels on RESET factory default On Output cancels on SILENCE ALARMS When the output status has been set press the ENTER button to return to...

Страница 27: ...other conventional SNDR1 SNDR2 and Twin Wire zone sounders will operate as normal A fire 470Ω signal to any other zone will operate ALL conventional SNDR1 SNDR2 and Twin Wire sounder circuits including the sounders connected to the interface zone as normal ZONE INTERFACE FUNCTION 1 2 3 ON 1 2 3 4 5 6 7 ZONE2 ZONE3 ZONE4 C NC NO NO C NC FIRE FAULT optional PANEL 1 PANEL 2 470Ω 3K3Ω Example connecti...

Страница 28: ...is enabled by default but can be disabled in the engineering functions To activate the controls using the key switch turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED will extinguish If the key switch is in the O...

Страница 29: ...ing correctly This function is operational without the need to activate controls Also has the numeric value 4 for code entry ENTER This button is used to confirm code entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 4 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 4 Indicates zone circuit is disabled or in test mode In...

Страница 30: ...ove the selection back to Zone 1 again When the desired circuit or output to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enabled Then use Disable Mode button again to move to the next circuit Any or all circuits can be disabled simultan...

Страница 31: ...ction back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next zone Any or all zones can be in test mode simultaneously When at the sounder status pos...

Страница 32: ...not active The following table shows details of the indications in fault diagnosis mode RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps LED Indicator State before pressing ENTER LED Pulsing after pressing ENTER LED Steady after pressing ENTER LED Off after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK...

Страница 33: ... 4 In the event of a false alarm look for the device that has caused the alarm A detector will have a In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer red LED lit or check to see if a call point glass is broken if so replace the glass or call an ...

Страница 34: ...onger compliant with this part of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the premises management to supervise all matters pertaining to the fire detection and fire alarm system The role of this person is to ensure that the system is tested and maintained in accordance with the recommend...

Страница 35: ... normally be a qualified electrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis The maximum period between inspections must not exceed six months Recommendations of BS5839 1 for periodic service visits include Every device on the system should be test...

Страница 36: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 34 ...

Страница 37: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 35 ...

Страница 38: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 36 ...

Страница 39: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 37 ...

Страница 40: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 38 ...

Страница 41: ...NTS IF ANY INITIALS OF TESTER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 39 ...

Страница 42: ... ALARMS FAULTS ENGINEERS VISITS Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 40 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Страница 43: ... ALARMS FAULTS ENGINEERS VISITS Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 41 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Страница 44: ... ALARMS FAULTS ENGINEERS VISITS Eclipse Installation Commissioning Operating Manual Approved Document Ref UI ECL 01 Issue 8 0 42 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details ...

Страница 45: ...arm look for the device that has caused the alarm A detector will have a In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer 5 5 When fully satis...

Страница 46: ......

Страница 47: ......

Страница 48: ...www haes tech com ...

Отзывы: