Esento Repeater Installation, Commissioning & Operating Manual
Approved Document Ref: DOC00985 Issue 6.0
19
OPERATING
Keypad
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND (red):
Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation.
SILENCE (blue):
Use to silence the sounders during an alarm condition.
RESET (green):
Resets the panel back to standby mode.
1: (Disable Mode)
With controls inactive, use to initialise code entry mode for activation of controls. With controls active,
use to disable zones, sounder circuits or aux outputs (see DISABLE MODE section). Also has the
numeric value 1 for code entry.
2: (Test Mode)
With controls inactive, use to initialise code entry mode for activation of controls. With controls active,
use to put zones or sounders circuits into test mode (see TEST MODE section). Also has the numeric
value 2 for code entry.
3: (Mute Buzzer)
Mutes the panels internal fire and fault buzzer. (The buzzer will still blip every 5-6 seconds during a
fire or fault condition). This function is operational without the need to activate controls. Also has the
numeric value 3 for code entry.
4: (Test Lamps &
Buzzer)
Use this button to illuminate all LEDs and sound the internal buzzer to check that they are working
correctly. This function is operational without the need to activate controls. Also has the numeric value
4 for code entry.
ENTER:
This button is used to confirm code entries. It can also be used for fault diagnosis (see FAULT
DIAGNOSIS section).
LED On
LED Pulsing
Zones in Fire 1 - 12
N/A
Indicates alarm condition in zone.
Zone Fault/Disabled/Test
1 - 12
Indicates zone circuit is disabled or in test
mode.
Indicates a fault in the zone circuit.
Supply Healthy:
Indicates mains and/or battery supply is
present.
N/A
General Fire:
N/A
Indicates panel is in alarm condition.
General Fault:
N/A
Indicates one or more faults are present.
General Disablement:
Indicates one or more circuits have been
disabled.
Indicates disablement selection mode is
active.
Test Mode:
Indicates one or more circuits are in test
mode
Indicates test mode selection is active.
Sounder Status:
Indicates sounder circuits have been
disabled or are in test mode
Indicates a fault on one or more sounder
circuits.
Aux Output Status:
Indicates auxiliary outputs have been
disabled.
N/A
Power Supply Fault:
N/A
Indicates a power supply or battery fault.
System Fault:
Indicates a system failure, panel not
functional or the internal PCB configuration
has not been set up correctly (see page 26).
Indicates the panel has recovered from a
system fault.
Access Level:
Indicates controls are active (access level 2).
Indicates panel is in configuration mode
(access level 3).
Repeater Fault:
N/A
Indicates a fault on one or more repeater
panels
Delay Status:
Delays are configured
Delay is running
Status LED Indicators
Содержание ESENTO 12