Esento Repeater Installation, Commissioning & Operating Manual
Approved Document Ref: DOC00985 Issue 6.0
16
SETUP & PROGRAMMING
4
4
4
3
Programming Repeater Panels
Programming of all the repeater panels is done from the main control panel.
The repeater panels have 2 inputs located on the main circuit board, Class Change (CC) and Alert (PUL).
Switching a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change
input (CC) will cause the alarms to sound continously and the Alert input (PUL) will cause the alarms to
pulse.
There are also 6 switch -ve outputs located on the Comms PCB. By default o/p 1 is set to activate on
common fire and o/p 2 is set to activate for common fault.
There are 4 programming options available for the inputs and outputs in the repeater panels.
•
Outputs 1 - 6 activate on common fire
•
Outputs 1 - 6 activate zonally for zones 1 - 6
•
Outputs 1 - 6 activate zonally for zones 7 - 12
•
Change inputs CC & PUL to power supply fault inputs.
It is also possible in this programming mode to disable the controls on repeater panels, making them
passive instead of active and to disable the battery monitoring on the repeater panel if no battery backup
is required.
A further option is provided (option 7), for use when used in a network, it is possible for the repeater to
mimic either the first 12 zones on a network or a particular control panel in the network. Details of the
repeater mimic display mode or shown over page.
Enter the above code and press ENTER. The zone 1 fire LED will light. This indicates which repeater panel
is to be programmed 1 - 8. Use button 1 to move the fire zone LED to the required repeater.
With the required repeater for editing LED lit, press the ENTER button to enter ‘editing mode’. The fire zone
1 LED will now pulse to indicate setting of attribute 1 (outputs 1 - 6 common fire) for that repeater.
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fire LED 1 - 7 as per table
below. Now use button 2 to change the setting indicated by the amber, fault LEDs, ON or OFF. Then use
button 1 again to move to the next attribute if required.
Fire LED (pulsing)
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
Attribute
O/P 1 - 6
Common Fire
O/P 1 - 6
Zonal (Zones
1 - 6)
O/P 1 - 6
Zonal (Zones
7 - 12)
Inputs For
PSU Fault
Controls
Passive
Disable Battery
Monitoring
Repeater
Mimic Display
Mode
Default Setting
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Содержание ESENTO 12