Esento Repeater Installation, Commissioning & Operating Manual

Approved Document Ref: DOC00985 Issue 6.0

16

SETUP & PROGRAMMING

4

4

4

3

Programming Repeater Panels

Programming of all the repeater panels is done from the main control panel.

The repeater panels have 2 inputs located on the main circuit board, Class Change (CC) and Alert (PUL). 
Switching a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change 
input (CC) will cause the alarms to sound continously and the Alert input (PUL) will cause the alarms to 

pulse.

There are also 6 switch -ve outputs located on the Comms PCB. By default o/p 1 is set to activate on 
common fire and o/p 2 is set to activate for common fault.

There are 4 programming options available for the inputs and outputs in the repeater panels.

• 

Outputs 1 - 6 activate on common fire

• 

Outputs 1 - 6 activate zonally for zones 1 - 6 

• 

Outputs 1 - 6 activate zonally for zones 7 - 12

• 

Change inputs CC & PUL to power supply fault inputs. 

It  is  also  possible  in  this  programming  mode  to  disable  the  controls  on  repeater  panels,  making  them 

passive instead of active and to disable the battery monitoring on the repeater panel if no battery backup 
is required.

A further option is provided (option 7), for use when used in a network, it is possible for the repeater to 
mimic either the first 12 zones on a network or a particular control panel in the network. Details of the 

repeater mimic display mode or shown over page.

Enter the above code and press ENTER. The zone 1 fire LED will light. This indicates which repeater panel 
is to be programmed 1 - 8. Use button 1 to move the fire zone LED to the required repeater.

With the required repeater for editing LED lit, press the ENTER button to enter ‘editing mode’. The fire zone 
1 LED will now pulse to indicate setting of attribute 1 (outputs 1 - 6 common fire) for that repeater.

Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fire LED 1 - 7 as per table 
below. Now use button 2 to change the setting indicated by the amber, fault LEDs, ON or OFF. Then use 
button 1 again to move to the next attribute if required. 

Fire LED (pulsing)

LED 1

LED 2

LED 3

LED 4

LED 5

LED 6

LED 7

Attribute

O/P 1 - 6 

Common  Fire

O/P 1 - 6 

Zonal (Zones 

1 - 6)

O/P 1 - 6 

Zonal (Zones 

7 - 12)

Inputs For 
PSU Fault

Controls 

Passive

Disable Battery 

Monitoring

Repeater 

Mimic Display 

Mode

Default Setting

OFF

OFF

OFF

OFF

OFF

OFF

OFF

Содержание ESENTO 12

Страница 1: ...Installation Commissioning Operating Manual 12 WAY FULLY FUNCTIONAL PASSIVE REPEATER PANEL Approved Document DOC00985 Issue 6 0 REPEATER PANEL S o f t w a r e V e r s i o n 4 0 A b o v e ...

Страница 2: ...ystem requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order Disclaimer No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manu...

Страница 3: ...IFICATION 6 POWER SUPPLY MODULE 7 INSTALLATION 8 SAFETY 8 ESD PRECAUTIONS 9 GENERAL 9 MOUNTING THE CABINET 9 MAINS CONNECTIONS 10 CONNECTING THE BATTERIES 11 CABLING 12 SETUP PROGRAMMING 14 INSTALL COMMS PCB IN MAIN CONTROL PANEL 14 SET NUMBER OF REPEATER PANELS ON MAIN CONTROL PANEL 15 REPEATER PANEL ADDRESSING 15 PROGRAMMING REPEATER PANELS 16 REPEATER MIMIC DSPLAY MODE 17 OPERATING 18 PANEL CON...

Страница 4: ...mms monitoring This then allows any topology of comms cabling to be utilised The main circuit board has 2 switch ve inputs which can be used to sound or pulse the alarms These inputs can also be re programmed for use as PSU fault inputs The internal comms PCB has 6 switch ve programmable outputs Different key types are used for the door lock and the activate controls key switch It is also possible...

Страница 5: ...Esento Repeater Installation Commissioning Operating Manual Approved Document Ref DOC00985 Issue 6 0 3 ABOUT THIS PANEL CABINET 57mm 80mm 260mm 308mm 250mm 300mm ...

Страница 6: ...prise of three circuit boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 BATTERY COMS A COMS B 28 V SW ve OUTPUTS 1 2 3 4 5 6 1 2 3 4 ON ADDRESS 1 2 3 4 ENTER RESOUND SILENCE RESET TPCA01 R Master PCB TPCA05 Comms PCB TPCA03 LED Display Controls PCB Piggy backs on Main PCB 6 programmable switch ve outputs ...

Страница 7: ... ZONE4 BATTERY 28v input for power supply Temperature compensation voltage control link Alert pulses sounders Precint class change activates sounders Switched ve inputs Switched ve outputs Max load 40mA To 0 volts COMS A COMS B 28 V SW ve OUTPUTS 1 2 3 4 5 6 1 2 3 4 ON ADDRESS Comms output to next panel Comms input from previous panel 28v output fused 500mA Switch ve O P Switch ve O P Switch ve O ...

Страница 8: ...s Outputs TPCA01 R Main PCB Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire PSU output Power supply voltage control line For temperature compensation control PSU Input 28vdc supply input Diode protected for reversal and independent short circuit Max current 3 amps Max input current 3 amps Input voltage 22vdc to 32vdc Inputs CC PUL Switched ve inputs connect to 0v to trigger Max input vol...

Страница 9: ...3mA Maximum ripple 250 millivolts Supply and charger fault monitored Min max battery size and type 2 x 3 2Ahr 12volt VRLA Use Yuasa NP range batteries Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval Battery charging voltage 27 3 vdc nominal at 20 deg C Temperature compensated Battery charging output current 1 5A PSU 630mA Current limited 10 Ohms Ba...

Страница 10: ... you are therefore requested to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned with its use This equipment is designed to be operated from 230V AC 50 60 Hz mains supplies and is of Class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation F...

Страница 11: ...parate power source Any coils or solenoids used in the system must be suppressed to avoid damage to the control equipment The site chosen for the location of the panel should be clean dry and not subject to shock or vibration Damp salt air or environments where water ingress or extremes of temperature may affect the panel must be avoided The temperature should be in the range 5 to 40 C and the rel...

Страница 12: ...y should be brought into the panel via one of the knockouts provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable ring crimp Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leavin...

Страница 13: ...o 1 minute until the monitoring cylce has finished polling This is normal If the fault doesn t clear after 1 minute check connections The battery charging voltage is factory calibrated to 27 3vdc 0 2v 20o C This should not normally require adjustment Where battery problems are experienced the following information should be considered a If a battery is disconnected from the charger no voltage will...

Страница 14: ...d in a loop as shown it is possible to re programme the panel back to legacy radial circuit comms monitoring This then allows any topology of comms cabling to be utilised To change the repeater comms monitoring type see over page 13 AllrepeaterprogrammingisdoneatthemaincontrolpanelwithLevel3programming mode active see main control panel instruction manual COMS A COMS B 28 V SW ve OUTPUTS 1 2 3 4 5...

Страница 15: ...the above code and press the ENTER button The 11 programmable options are represented by fire zone LEDs 1 11 Option 6 being the change repeater comms monitoring type setting Use button 1 to move to option 6 RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps Fire LED Programming Option 1...

Страница 16: ... PCB to re connect the display board ribbon cable Once the Comms PCB has been fitted to the control panel switch 7 on the 7 way DIL switch located on the main circuit board should be switched to the ON position With this switch in the ON position the panel will automatically recognise operate the Comms PCB TPCA05 Next the control panel will need to be programmed for the number of repeater panels o...

Страница 17: ...button 1 to move to option 2 RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps Fire LED Programming Option 1 Change remove keypad access code 2 Set number of repeater panels on system 3 Set output delay time 1 10 minutes 4 Turn off battery monitoring 5 Set up internal PCB configuration...

Страница 18: ...ve and to disable the battery monitoring on the repeater panel if no battery backup is required A further option is provided option 7 for use when used in a network it is possible for the repeater to mimic either the first 12 zones on a network or a particular control panel in the network Details of the repeater mimic display mode or shown over page Enter the above code and press ENTER The zone 1 ...

Страница 19: ...tton to invoke edit mode The current setting is displayed in a binary code using LEDs 7 8 9 10 as per table below Whilst in edit mode use buttons 2 4 respectively to increment or decrement the binary indications to the required setting as descibed in the table Option zone 7 fire LED pulsing Zone 7 Fault LED Zone 8 Fault LED Zone 9 Fault LED Zone 10 Fault LED Repeat Master Panel OFF OFF OFF OFF Rep...

Страница 20: ...de entry to activate the controls is enabled by default but can be disabled in the Level 3 engineering functions To activate the controls using the key switch Turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED wil...

Страница 21: ...rational without the need to activate controls Also has the numeric value 4 for code entry ENTER This button is used to confirm code entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 12 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 12 Indicates zone circuit is disabled or in test mode Indicates a fault in the zone circ...

Страница 22: ... and finally to the Delay LED Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enabled Then use Disable Mode button agai...

Страница 23: ...sing the button once more will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next zone Any or all zones can be in test mode s...

Страница 24: ...www haes systems com ...

Отзывы: