Esento Repeater Installation, Commissioning & Operating Manual

Approved Document Ref: DOC00985 Issue 6.0

9

INSTALLATION

ESD PRECAUTION

GENERAL

MOUNTING THE CABINET

Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD wrist strap, 

suitably grounded, should be worn at all times when handling pcbs. These wrist straps are designed to 
prevent the build up of static charges, not only within a persons body, but on many other materials. 

ESD damage is not always evident immediately, faults can manifest themselves at anytime in the future.
All pcbs should be stored in static shielded bags (silvered) for safe keeping, when not mounted in the 

control panel. 

Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely 

to induce electrical interference. Earth links should be maintained on all system cables and grounded in 

the control panel. The detection and sounder circuit cabling is classed as extra low voltage and must be 
segregated away from mains voltage.

• 

Any junction boxes used should be clearly labelled FIRE ALARM.

• 

Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.

• 

Any coils or solenoids used in the system must be suppressed, to avoid damage to the control 

equipment.

The site chosen for the location of the panel should be clean, dry and not subject to shock or vibration. 

Damp, salt air or environments where water ingress or extremes of temperature may affect the panel must 

be avoided. The temperature should be in the range -5° to +40°C, and the relative humidity should not 
exceed 95%.

Before mounting the cabinet remove the main PCB.

Remove the power supply module connecting wires from the main PCB, taking care to note where to re-
connect them. The main PCB can then be carefully pulled off it’s mounting clips.

Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted 

level and in a convenient location where it may be easily operated and serviced.

External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove 
any knockouts and ensure the cabinet is clear of swarf etc prior to refitting the PCB. Always ensure that if 
a knockout is removed, the hole is filled with a good quality cable gland. Any unused knockouts must be 

securely blanked off.

Knockouts should be removed with a sharp tap at the 
rim  of  the  knockout  using  a  flat  6mm  broad  bladed 

screwdriver.

Use  of  excessive  force  will  damage  the  enclosure 

around the knockout.

Содержание ESENTO 12

Страница 1: ...Installation Commissioning Operating Manual 12 WAY FULLY FUNCTIONAL PASSIVE REPEATER PANEL Approved Document DOC00985 Issue 6 0 REPEATER PANEL S o f t w a r e V e r s i o n 4 0 A b o v e ...

Страница 2: ...ystem requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order Disclaimer No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole The manu...

Страница 3: ...IFICATION 6 POWER SUPPLY MODULE 7 INSTALLATION 8 SAFETY 8 ESD PRECAUTIONS 9 GENERAL 9 MOUNTING THE CABINET 9 MAINS CONNECTIONS 10 CONNECTING THE BATTERIES 11 CABLING 12 SETUP PROGRAMMING 14 INSTALL COMMS PCB IN MAIN CONTROL PANEL 14 SET NUMBER OF REPEATER PANELS ON MAIN CONTROL PANEL 15 REPEATER PANEL ADDRESSING 15 PROGRAMMING REPEATER PANELS 16 REPEATER MIMIC DSPLAY MODE 17 OPERATING 18 PANEL CON...

Страница 4: ...mms monitoring This then allows any topology of comms cabling to be utilised The main circuit board has 2 switch ve inputs which can be used to sound or pulse the alarms These inputs can also be re programmed for use as PSU fault inputs The internal comms PCB has 6 switch ve programmable outputs Different key types are used for the door lock and the activate controls key switch It is also possible...

Страница 5: ...Esento Repeater Installation Commissioning Operating Manual Approved Document Ref DOC00985 Issue 6 0 3 ABOUT THIS PANEL CABINET 57mm 80mm 260mm 308mm 250mm 300mm ...

Страница 6: ...prise of three circuit boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 BATTERY COMS A COMS B 28 V SW ve OUTPUTS 1 2 3 4 5 6 1 2 3 4 ON ADDRESS 1 2 3 4 ENTER RESOUND SILENCE RESET TPCA01 R Master PCB TPCA05 Comms PCB TPCA03 LED Display Controls PCB Piggy backs on Main PCB 6 programmable switch ve outputs ...

Страница 7: ... ZONE4 BATTERY 28v input for power supply Temperature compensation voltage control link Alert pulses sounders Precint class change activates sounders Switched ve inputs Switched ve outputs Max load 40mA To 0 volts COMS A COMS B 28 V SW ve OUTPUTS 1 2 3 4 5 6 1 2 3 4 ON ADDRESS Comms output to next panel Comms input from previous panel 28v output fused 500mA Switch ve O P Switch ve O P Switch ve O ...

Страница 8: ...s Outputs TPCA01 R Main PCB Terminal capacity 0 5mm2 to 2 5mm2 solid or stranded wire PSU output Power supply voltage control line For temperature compensation control PSU Input 28vdc supply input Diode protected for reversal and independent short circuit Max current 3 amps Max input current 3 amps Input voltage 22vdc to 32vdc Inputs CC PUL Switched ve inputs connect to 0v to trigger Max input vol...

Страница 9: ...3mA Maximum ripple 250 millivolts Supply and charger fault monitored Min max battery size and type 2 x 3 2Ahr 12volt VRLA Use Yuasa NP range batteries Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval Battery charging voltage 27 3 vdc nominal at 20 deg C Temperature compensated Battery charging output current 1 5A PSU 630mA Current limited 10 Ohms Ba...

Страница 10: ... you are therefore requested to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned with its use This equipment is designed to be operated from 230V AC 50 60 Hz mains supplies and is of Class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation F...

Страница 11: ...parate power source Any coils or solenoids used in the system must be suppressed to avoid damage to the control equipment The site chosen for the location of the panel should be clean dry and not subject to shock or vibration Damp salt air or environments where water ingress or extremes of temperature may affect the panel must be avoided The temperature should be in the range 5 to 40 C and the rel...

Страница 12: ...y should be brought into the panel via one of the knockouts provided A suitable cable gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using a suitable ring crimp Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leavin...

Страница 13: ...o 1 minute until the monitoring cylce has finished polling This is normal If the fault doesn t clear after 1 minute check connections The battery charging voltage is factory calibrated to 27 3vdc 0 2v 20o C This should not normally require adjustment Where battery problems are experienced the following information should be considered a If a battery is disconnected from the charger no voltage will...

Страница 14: ...d in a loop as shown it is possible to re programme the panel back to legacy radial circuit comms monitoring This then allows any topology of comms cabling to be utilised To change the repeater comms monitoring type see over page 13 AllrepeaterprogrammingisdoneatthemaincontrolpanelwithLevel3programming mode active see main control panel instruction manual COMS A COMS B 28 V SW ve OUTPUTS 1 2 3 4 5...

Страница 15: ...the above code and press the ENTER button The 11 programmable options are represented by fire zone LEDs 1 11 Option 6 being the change repeater comms monitoring type setting Use button 1 to move to option 6 RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps Fire LED Programming Option 1...

Страница 16: ... PCB to re connect the display board ribbon cable Once the Comms PCB has been fitted to the control panel switch 7 on the 7 way DIL switch located on the main circuit board should be switched to the ON position With this switch in the ON position the panel will automatically recognise operate the Comms PCB TPCA05 Next the control panel will need to be programmed for the number of repeater panels o...

Страница 17: ...button 1 to move to option 2 RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps Fire LED Programming Option 1 Change remove keypad access code 2 Set number of repeater panels on system 3 Set output delay time 1 10 minutes 4 Turn off battery monitoring 5 Set up internal PCB configuration...

Страница 18: ...ve and to disable the battery monitoring on the repeater panel if no battery backup is required A further option is provided option 7 for use when used in a network it is possible for the repeater to mimic either the first 12 zones on a network or a particular control panel in the network Details of the repeater mimic display mode or shown over page Enter the above code and press ENTER The zone 1 ...

Страница 19: ...tton to invoke edit mode The current setting is displayed in a binary code using LEDs 7 8 9 10 as per table below Whilst in edit mode use buttons 2 4 respectively to increment or decrement the binary indications to the required setting as descibed in the table Option zone 7 fire LED pulsing Zone 7 Fault LED Zone 8 Fault LED Zone 9 Fault LED Zone 10 Fault LED Repeat Master Panel OFF OFF OFF OFF Rep...

Страница 20: ...de entry to activate the controls is enabled by default but can be disabled in the Level 3 engineering functions To activate the controls using the key switch Turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off position and the Access Level indicator LED wil...

Страница 21: ...rational without the need to activate controls Also has the numeric value 4 for code entry ENTER This button is used to confirm code entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 12 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 12 Indicates zone circuit is disabled or in test mode Indicates a fault in the zone circ...

Страница 22: ... and finally to the Delay LED Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enabled Then use Disable Mode button agai...

Страница 23: ...sing the button once more will move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next zone Any or all zones can be in test mode s...

Страница 24: ...www haes systems com ...

Отзывы: