Haefely WA 2293 Скачать руководство пользователя страница 6

U

(A)

V

(B)

W

(C)

Voltage to U (A)

100%

66%

33%

Voltage to V (B)

50%

100%

50%

Voltage to W (C)

33%

66%

100%

The main function of the on load tap changer is to switch between 

transformer taps without interrupting the current. The 2293 

registers the current while tap changer is operated and records 

the values at a defined sample rate.

Discontinuities or deviations between different taps are a sign 

of tap changer fault.

TAP CHANGER - DYNAMIC RESISTANCE 

The tap changer test with the 2293 is done automatically and 

without reconnection. In addition, the tap changer control 

accessory allows a complete automatic sequence without 

human intervention.

Calculation of the main curve parameters like time to rise, time 

to fall or delta, for failure detection, is automatically done.

Magnetic balance test is performed to detect faults in the 

magnetic core. The test looks for changes in the reluctance 

of the magnetic circuit caused by defects in the magnetic 

core structure, shifting or shape changes in the windings or 

inter turn insulation fault.

The test is performed on three phase transformers by 

applying a voltage on one of the phases and measures the 

voltage on the other two. The induced voltage will depend 

on the limb position into the core as the following table.

The 2293 performs the magnetic balance test automatically 

and without any reconnection. Test results are shown 

graphically for a better understanding.

Imbalances will be graphically noted including the involved 

phases.

Short circuit impedance is a routine test done to all 
transformers after manufacture and specified in the 
transformer nameplate.

Changes in the short circuit impedance along transformer 

life is normally an indication of mechanical damages.

The 2293 automatically performs a short circuit impedance 

test at reduced voltage on power and distribution 
transformers and calculates the three phase equivalent 
short circuit impedance for comparison with previous test or 
with nameplate values.

After a power or distribution transformer is disconnected 

from the power grid or when a DC current is applied to it, for 
example during a routine winding resistance measurement, 
the transformer core is likely to have some remnant 
magnetism. This remnant magnetism will generate high 

over currents when the transformer is reconnected to the 
grid, and this is commonly known as transformer inrush 
current.

In addition, magnetic remnant has an adverse effect on 

other measurements like FRA or TTR.

The 2293 includes a fully automatic demagnetisation feature 

which eliminates the magnetic remnant. Select the winding 
where demagnetisation needs to be performed and press 
start. The unit visualizes the whole demagnetisation cycle 
and performs the correct core demagnetisation in seconds.

MAGNETIC BALANCE TEST

SHORT CIRCUIT IMPEDANCE

DEMAGNETISATION FUNCTION

10

11

Содержание WA 2293

Страница 1: ...Designed by WA 2293 Automatic Transformer Winding Analyser Leaflet ...

Страница 2: ...sistance turns ratio arbitrary phase vector group check demagnetization dynamic resistance short circuit impedance magnetic balance and heat run test heat rise and cooling curve Once connected can perform all tests in all phases on both windings More compact and lightweight solution in comparison to traditional equipment with up to 100A test current Easy operation Fully automated twinding resistan...

Страница 3: ... transformers like phase shifting or arc furnace which don t follow the standard 30 phase steps can be easily measured DYNAMIC RESISTANCE ON TAP CHANGER Dynamic resistance measurement is a reliable check of the transformer tap changer Discontinuities or deviations between different taps are signs of tap changer fault SHORT CIRCUIT IMPEDANCE Changes in the short circuit impedance along transformer ...

Страница 4: ...n be turned off at any point of time to disconnect the device thereby guarenteeing complete safety Quick Connection System The twin lock connectors and the one time connection system help to reduce connecting time drastically TemperatureMeasurement Temperature probes inputs 6 included up to 30 with the 2293 TEMPEXT to monitor the test object temperature during resistance measurement or heat run te...

Страница 5: ...bitrary phase shifts or those that do not follow the 30 phase steps between the primary and secondary winding are common in special transformers like phase shifting rectifier furnace and traction transformers With the optional arbitrary phase shift software key 2293 SKAP the 2293 can measure turns and voltage ratio phase displacement and excitation current of these special type transformers The sp...

Страница 6: ...ithout any reconnection Test results are shown graphically for a better understanding Imbalances will be graphically noted including the involved phases Short circuit impedance is a routine test done to all transformers after manufacture and specified in the transformer nameplate Changes in the short circuit impedance along transformer life is normally an indication of mechanical damages The 2293 ...

Страница 7: ...vailable magnetic and liquids temperature probes 2293 TEMP2 2293 TEMP1 are easily connected to the transformer Probe configuration is done graphically oil radiator top radiator bottom ambient In addition pre configured tests according to ANSI and IEC standards are included calculating the transformer temperature in real time and informing when stabilization is reached For the cooling curve the 229...

Страница 8: ...2823 Including Winding resistance measurement Demagnetization measurement Heat run Cooling curve measurement 8 measuring cables of 10 m length equipped with Kelvin probes Cable bag Test certificate Instruction manual 1 2 3 Measurement Cables Clamps Extension cable 10 m high voltage side Extension cable 10 m low voltage side 2293 10HV 2293 10LV Additional measuring cables HV LV 8 cables 3 m length ...

Страница 9: ...G Birsstrasse 300 4052 Basel Switzerland 41 61 373 4111 sales haefely com www haefely com CHINA HAEFELY AG Representative Office 8 1 602 Fortune Street No 67 Chaoyang Road Beijing 100025 China 86 10 8578 8099 sales haefely com cn www haefely com INDIA HAEFELY India Service Office C o Pfiffner Instrument Transformers Pvt Ltd 176 178 2 Sarul Viholi Nashik 422 010 India 1 800 266 4052 toll free sales...

Отзывы: