16
14.1. Fault – error code Fxxx
Code
Cause:
Correction:
F001
A.
STL triggered due to overheating
B.
Fuse (F1) in the central unit is defective
C.
Ignition short circuit
A.
If STB has triggered - contact service
department
B.
Fuse F1(3.15 A) defective - contact service
department
C.
Ignition defective - contact service department
F002
A.
Burner dirty
B.
Pellet tank empty
C.
Ignition defective
D.
Burner not lying flush
E.
Flame temperature sensor defective
F.
Downpipe / screw conveyor blocked
G.
Screw motor defective
A.
Clean burner
B.
Clean burner - fill pellet tank
C.
Ignition defective - contact service department
D.
Clean burner - position burner correctly
E.
Flame temperature sensor defective - contact
service department
F.
Clean the intake on the screw conveyor
housing with a vacuum cleaner - clean burner
G.
Screw motor defective - contact service
department
F003
A.
Heat exchanger / smoke flues dirty
B.
Heating curve set too low
C.
Room temperature sensor is lying on the
floor or wall
A.
Cleaning the smoke flues - clean burner
B.
Clean burner - Adjust heating curve as
described
C.
Clean burner - suspend room temperature
sensor freely
F005
A.
Burner dirty
B.
Pellet tank empty
C.
Downpipe / screw conveyor blocked
D.
Room too airtight – required combustion
air cannot flow into the room
E.
Flue gas temperature sensor defective
F.
Screw motor defective
G.
Pellet fuel has too low a calorific value
A.
Clean burner
B.
Clean burner - fill pellet tank
C.
Clean the intake on the screw conveyor
housing with a vacuum cleaner. – Clean
burner
D.
Clean burner - Ensure adequate combustion
air
E.
Flue gas temperature sensor defective -
contact service department
F.
Screw motor defective - contact service
department
G.
Clean burner - switch to high quality pellet
type
F006
A.
Combustion chamber door open during
operation
B.
Damper in front of the door contact switch
not in the right position
C.
Cable broken in the electric wiring to the door
contact switch
D.
The connector has come out on the door
contact switch or on the central unit
A.
Clean burner - close door
B.
Clean burner - Adjust damper in front of the
door contact switch
C.
Cable broken on door contact switch - contact
service department
D.
Contact service department
F007
A.
Flue gas temperature sensor defective or
not connected
A.
Contact service department
F008
A.
Flue gas temperature sensor defective
A.
Contact service department
F009
A.
Note: Combustion chamber door open
during “Off or standby”
A.
No correction necessary - Close door - Error is
automatically cleared
F011
A.
Room temperature sensor defective or
not connected
A.
Contact service department
F012
A.
Room temperature sensor defective
A.
Contact service department
F015
A.
Induced draught fan defective
B.
Power supply to the fan motor interrupted
A.
Contact service department
B.
Check cable - contact service department
F018
A.
Power cut
A.
Clean burner - Clear error 018