13
Procedure:
The required value can be selected with the
“Plus”
or
“Minus”
buttons.
The setting is saved by pressing the
“OK”
button.
To exit the function, press the
“On/Off”
button.
9.1.9. Software version information
↱
↓
Info Software
SW-Version: HSP-6-V5.03
test date: 2015-02-11
Procedure:
To exit the function, press the
“On/Off”
button.
9.1.10.
Test setting
Heating in the test position is only permitted by specialists of various
test laboratories!
In this menu, the partial load / nominal load is tested according to EN 14785
standard.
Procedure:
Use the "
Plus
" or "
Minus
" keys to enter the required code.
The code is as follows:
1854
Pressing the "
OK
" button saves the setting.
The test setting partial load or nominal load is then selected.
Pressing the "
OK
" button activates the "
START
" of the respective test setting.
10. Operating statuses:
10.1. Start Zone 1-20 ( Start phase )
The start phase begins if:
the current room temperature falls below the set target temperature by 1°C
the stove is cooled down to a temperature below 70 C°
During the “Start phase”, the burner tray is filled with a precisely defined amount of fuel and this fuel is ignited using
an electric ignition.
The whole “Start phase” can go through up to 20 zones. It finishes after reaching a precisely defined temperature at
the “flame temperature sensor” and the control system puts the stove into “Heating mode”.
The duration of the “Start phase” can therefore vary.
If, during the start phase, no flame generation can be achieved or the required temperature at the “flame temperature
sensor” cannot be reached, a switch-off process is initiated.
Typ
Chimney draft at nominal heat output / partial load
HSP 1, HSP 2
11 / 7 Pa
HSP 6
11 / 5 Pa
HSP 8
11 / 6 Pa
↱
+ -
OK
" * "
Test setting