System Power Available : 300 watts
System Power Per Unit : 650 watts
System Power Reserved : 200 watts
System Power AlarmFlag : 0x00000000
Slot Board Type Watts Priority
------------------------------------------------------------
0 RSE-X3 0(0) 0(0)
1 RSE-X3 0(0) 0(0)
2 NA 0(0) 0(0)
3 FIP-300 150(0)* 5(-1)
c.
If the available power is sufficient, display detailed LPU status information.
[System-probe]display hardware internal sysm fip
Slot No. State Errcode Flags HwFlags
--------------------------------------------------------------
2 Off 0 0x0 0x0
3 enable 0 0x3 0x43
Flags :
bit0-PowerOn bit1-Present
bit2-ManuOn bit3-ManuOff
bit4-AutoOff bit5-Inserting
bit6-Enable
−
If the
State
field displays
enable
, the LPU might have hardware problems. Replace the
LPU.
−
If the
State
field displays
Fault
, the LPU might have a BOM code error or the device
does not support the LPU. Update the BOM code or replace the LPU.
−
If the
State
field displays
Disable
, the LPU might have been unmounted. Use the
undo
remove slot
command to mount the LPU.
3.
If the LPU has been powered on, the basic BootWare segment might have been corrupted.
Contact H3C Support.
4.
Reboot the device.
5.
Identify whether the Comware image files have been correctly loaded:
If the following information is displayed repeatedly, the IPC channel is not available.
Press Ctrl+B to enter extended boot menu......
Failed. No response received from the active MPU.
GDSYNC_SendRequest: Start
GDSYNC_SendRequest: Start
GDSYNC_SendRequest: Start
GDSYNC_SendRequest: Start
GDSYNC_SendRequest: Start
GDSYNC_Start failed!
SYNC failed.
Replace the LPU with an LPU that can operate correctly. Install the original module in
another slot.
−
If neither of the LPU can start up correctly either, the MPU or LPU might have problems.
Contact H3C Support.