background image

 

2-5 

Figure2-10 S6805-54HT chassis dimensions with the mounting brackets installed at the 

power supply side 

 

(1) Power supply handle 

(2) Mounting bracket 

 

Follow these guidelines when you install the switch in a 19-inch rack: 

 

The distance between the front and rear posts of the rack must meet the requirements 

described in 

Table2-3

. 

 

To secure the switch to the rack, you must install not only mounting brackets, but also chassis 

rails and slide rails. 

Table2-3 Distance requirements between the front and rear rack posts 

Switch model 

Installation method 

Distance between the front and 

rear rack posts 

S6805-54HF 

Using mounting brackets and rack 

mounting rail kit A (long slide rails) 

621 mm to 793 mm (24.45 in to 31.22 in) 

Using mounting brackets and rack 

mounting rail kit B (super-short slide rails, 

narrow-spacing installation) 

330 mm to 505 mm (12.99 in to 19.88 in) 

Using mounting brackets and rack 

mounting rail kit B (super-short slide rails, 

wide-spacing installation) 

438 mm to 632 mm (17.24 in to 24.88 in) 

S6805-54HT 

Using mounting brackets and rack 

mounting rail kit A (long slide rails) 

621 mm to 854 mm (24.45 in to 33.62 in) 

Using mounting brackets and rack 

mounting rail kit C 

401 mm to 634 mm (15.79 in to 24.96 in) 

 

Table2-4 Chassis dimensions and rack depth requirements 

Device 

model 

Chassis dimensions 

Rack depth requirement 

S6805-54HF 

 

Height

—44 mm (1.73 in) (1 RU) 

 

Width

—440 mm (17.32 in). 

 

Total depth

—425 mm (16.73 in) 

 

25 mm (0.98 in) for the power 

supply or fan tray handle 

 

400 mm (15.75 in) for the 

chassis. 

To ensure that the rack door can be closed 

easily after cables are connected, make sure 

the rack meets the following requirements: 

 

A minimum of 800 mm (31.50 in) in depth 

(recommended) 

 

A minimum of 130 mm (5.12 in) from the 

front rack post to the front door 

 

A minimum of 449 mm (17.68 in) from 

the front rack post to the rear door 

Содержание S6805 Series

Страница 1: ...H3C S6805 Switch Series Installation Guide New H3C Technologies Co Ltd http www h3c com Document version 5W100 20200324...

Страница 2: ...espective owners Notice The information in this document is subject to change without notice All contents in this document including statements information and recommendations are believed to be accur...

Страница 3: ...x choices keywords or arguments that are optional x y Braces enclose a set of required syntax choices separated by vertical bars from which you select one x y Square brackets enclose a set of optional...

Страница 4: ...s a Layer 2 or Layer 3 switch or a router that supports Layer 2 forwarding and other Layer 2 features Represents an access controller a unified wired WLAN module or the access controller engine on a u...

Страница 5: ...Documentation feedback You can e mail your comments about product documentation to info h3c com We appreciate your comments...

Страница 6: ...cord 2 18 Connecting the power cord for a PSR450 12A PSR450 12A1 power supply 2 19 Connecting the power cord for a PSR450 12AHD power supply 2 19 Connecting the DC power cord for a PSR450 12D power s...

Страница 7: ...cifications 6 3 7 Appendix B FRUs and compatibility matrixes 7 1 Power supplies 7 1 Fan trays 7 2 8 Appendix C Ports and LEDs 8 1 Ports 8 1 Console port 8 1 Management Ethernet port 8 1 USB port 8 2 S...

Страница 8: ...grounding cable before power on Make sure the operating voltage is in the required range To avoid electrical shocks do not open the chassis while the switch is operating or when the switch is just po...

Страница 9: ...humidity is low In the worst case electrostatic adsorption can cause communication failure Table1 1 Dust concentration limit in the equipment room Substance Particle diameter Concentration limit Dust...

Страница 10: ...r light Do not stare into beams or view directly with optical instruments when the switch is operating Installation tools No installation tools are provided with the switch Prepare the following tools...

Страница 11: ...provided All S6805 models N A Grounding screw 2 provided All S6805 models 2114A09C Power supply filler panel 1 provided All S6805 models N A Releasable cable tie User supplied All S6805 models 040429...

Страница 12: ...thereby CAUTION Always wear an ESD wrist strap during the installation process Make sure the wrist strap makes good skin contact and is reliably grounded Figure2 1 Hardware installation flow Start In...

Страница 13: ...rack mounting rail kit B including one pair of chassis rails and one pair of super short slide rails optional See Figure2 4 S6805 54HT 1U high one pair provided See Figure2 2 1U rack mounting rail ki...

Страница 14: ...f is available you can put the switch on the rack shelf slide the switch to an appropriate location and attach the switch to the rack with the mounting brackets 1 2 1 2 Attach the mounting brackets to...

Страница 15: ...port side 1 Power supply handle 2 Mounting bracket Figure2 8 S6805 54HF chassis dimensions with the mounting brackets installed at the power supply side 1 Power supply handle 2 Mounting bracket Figure...

Страница 16: ...tallation 330 mm to 505 mm 12 99 in to 19 88 in Using mounting brackets and rack mounting rail kit B super short slide rails wide spacing installation 438 mm to 632 mm 17 24 in to 24 88 in S6805 54HT...

Страница 17: ...network port side and one near the power supply side The switch provides a primary grounding point with a grounding sign and an auxiliary grounding point The S6805 54HF and S6805 54HT switches are ide...

Страница 18: ...ed to attach the chassis rail to the chassis For installation of chassis rails of rack mounting rail kit A long slide rails and rack mounting rail kit C see Figure2 12 Figure2 15 Figure2 18 and Figure...

Страница 19: ...g installation Figure2 15 Attaching the mounting brackets and chassis rails to an S6805 54HF switch mounting brackets installed near the power supply side rack mounting rail kit A Figure2 16 Attaching...

Страница 20: ...ounting rail kit A or C Figure2 19 Attaching the mounting brackets and chassis rails to an S6805 54HT switch mounting brackets installed near the power supply side rack mounting rail kit A or C Connec...

Страница 21: ...ts are used to attach the slide rails to the rack Prepare M6 screws and cage nuts yourself As a best practice use a torque of 30 kgf cm 2 94 Nm to fasten the M6 screws Before mounting the switch in th...

Страница 22: ...ack posts and make sure they are at the same level as the slide rails 5 One person performs the following operations a Supporting the bottom of the switch aligns the chassis rails with the slide rails...

Страница 23: ...igure2 22 Mounting an S6805 54HF switch in the rack mounting brackets installed near the power supply side Figure2 23 Mounting an S6805 54HF switch in the rack mounting brackets installed near the por...

Страница 24: ...ground commonly known as PGND You must securely connect this chassis ground to the earth so the faradism and leakage electricity can be safely released to the earth to minimize EMI susceptibility of...

Страница 25: ...NSA or LSPM1FANSB fan tray 1 Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded 2 Unpack the fan tray and verify that the fan tray model is correct 3 Orient the...

Страница 26: ...eir specifications see Power supplies Precautions Provide a separate circuit breaker for each power supply Do not install power supplies of different model on the same switch To avoid device damage an...

Страница 27: ...nce while inserting the power supply pull out the power supply and insert it again Figure2 29 Installing a power supply IMPORTANT If the target power supply slot has a filler panel installed first rem...

Страница 28: ...n an antistatic bag for future use Figure2 31 Removing a PSR250 12A power supply 1 Pivot the latch to the right with your thumb 2 Pull the power supply out Removing a PSR450 12AHD power supply The fol...

Страница 29: ...n contact and is reliably grounded 2 Use a flat head screwdriver to loosen the screws on the power cord connector and then pull the connector out to remove the power cord See Figure2 34 3 Hold the han...

Страница 30: ...the cable tie to secure the power cord to the handle of the power supply Connecting the power cord for a PSR450 12AHD power supply 1 Slide the cable clamp onto the tie mount on the power supply as sho...

Страница 31: ...nector into the power receptacle on the power supply If you orient the DC power cord connector upside down you cannot insert the connector into the power receptacle 2 Use a flat head screwdriver to fa...

Страница 32: ...is stable The grounding cable is securely connected The power source is as required by the switch The power cords are correctly connected If part of the network cable for a port is routed outdoors ver...

Страница 33: ...able yourself In the following figure the switch is connected to a PC from the serial console port Figure3 1 Connecting the switch to a terminal from the serial console port Connecting the serial cons...

Страница 34: ...has a USB mini Type B connector at one end to connect to the Mini USB console port of the switch and a standard USB Type A connector at the other end to connect to the USB port on the configuration te...

Страница 35: ...3 3 Figure3 3 Device Driver Installation Wizard 6 Click Continue Anyway if the following dialog box appears Figure3 4 Software Installation 7 Click Finish...

Страница 36: ...e programs Configure the terminal parameters as follows Bits per second 9600 Data bits 8 Stop bits 1 Parity None Flow control None Starting the switch 1 Before powering on the switch verify that the f...

Страница 37: ...hing release notes for the device 3 After the startup completes you can access the CLI to configure the switch For more information about the configuration commands and CLI see H3C S6805 S6850 S9850 S...

Страница 38: ...manageability The switch can set up an IRF fabric only with switches from the same switch series IRF fabric setup flowchart Figure4 1 IRF fabric setup flowchart Start Plan IRF fabric setup Install IR...

Страница 39: ...tch automatically reboot and the IRF fabric is established Planning IRF fabric setup This section describes issues that an IRF fabric setup plan must cover Planning IRF fabric size and the installatio...

Страница 40: ...gy the failure of one IRF link does not cause the IRF fabric to split as in daisy chain topology Rather the IRF fabric changes to a daisy chain topology without interrupting network services You conne...

Страница 41: ...ables to connect the switches for IRF connections If the IRF member switches are far away from one another choose QSFP QSFP28 transceiver modules and optical fibers If the IRF member switches are all...

Страница 42: ...in different racks side by side to deploy a top of rack ToR solution Figure4 6 shows an example for connecting four top of rack IRF member switches by using QSFP28 cables and QSFP28 transceiver module...

Страница 43: ...basic functionality of the IRF fabric 1 Log in to the IRF fabric through the console port of any member switch 2 Create a Layer 3 interface assign it an IP address and make sure the IRF fabric and th...

Страница 44: ...eptable range and good ventilation is provided for the power supply 4 If the issue persists contact the H3C Support To replace a power supply see Installing and removing a power supply Fan tray failur...

Страница 45: ...Baud rate 9600 Data bits 8 Stop bits 1 Parity None Flow control None 4 If the issue persists contact H3C Support Garbled display on the configuration terminal Symptom The configuration terminal displa...

Страница 46: ...ray 5 10 Power supply 1 11 Power supply 2 12 System status LED SYS 13 Serial label pull tab 14 Copper management Ethernet port LED LINK ACT 15 Copper management Ethernet port 16 Fiber management Ether...

Страница 47: ...ft side panel 1 Primary grounding point 2 Auxiliary grounding point S6805 54HT Figure6 4 Front panel 1 1 10GBASE T autosensing Ethernet port 2 1 10GBASE T autosensing Ethernet port LED 3 QSFP28 port 4...

Страница 48: ...ing a fan tray see Installing and removing a fan tray Figure6 6 Left side panel 1 Primary grounding point 2 Auxiliary grounding point Technical specifications Table6 1 Technical specifications Item S6...

Страница 49: ...HD Single DC input 91 W Dual DC inputs 102 W PSR450 12D Single DC input 94 W Dual DC inputs 101 W Maximum power consumption PSR450 12A PSR450 12A1 Single AC input 208 W Dual AC inputs 213 W PSR450 12A...

Страница 50: ...PSR450 12A1 0231A6NC Yes Yes PSR450 12AHD 0231A6NA Yes Yes PSR450 12D 0231A6NB Yes Yes Fan trays LSPM1FANSA 0231ACJM Yes Yes LSPM1FANSB 0231ACJL Yes Yes Power supplies CAUTION When the switch has two...

Страница 51: ...tage range 48 to 60 VDC Max input voltage range 36 to 72 VDC Max output power 450 W Fan trays Table7 3 Fan tray specifications Item Specifications LSPM1FANSA Dimensions 41 40 105 mm 1 61 1 57 4 13 in...

Страница 52: ...7 3 Item Specifications Documentation reference H3C LSPM1FANSA LSPM1FANSB Fan Trays User Guide...

Страница 53: ...ransmission baud rate 9600 bps default to 115200 bps Services Provides connection to an ASCII terminal Provides connection to the serial port of a local or remote through a pair of modems PC running t...

Страница 54: ...ompliant USB2 0 port that can upload and download data at a rate up to 480 Mbps You can use this USB port to access the file system on the flash file system of the switch for example to upload or down...

Страница 55: ...Single mode 9 125 N A 40 km 24 86 miles SFP GE LH40 SM1550 1550 LC Single mode 9 125 N A 40 km 24 86 miles SFP GE LH80 SM1550 1550 LC Single mode 9 125 N A 80 km 49 71 miles Table8 6 10 Gigabit SFP t...

Страница 56: ...r cables in Table8 14 Table8 9 QSFP28 transceiver modules available for the QSFP28 ports Model Central wavelength nm Connector Cable Fiber type and diameter m Modal bandwidth MHz km Max transmission d...

Страница 57: ...dwidth MHz km Max transmission distance QSFP 40G SR 4 MM850 850 MPO PC polished 12 fiber Multi mode 50 125 2000 100 m 328 08 ft 4700 150 m 492 12 ft QSFP 40G CS R4 MM850 850 MPO PC polished 12 fiber M...

Страница 58: ...ted pair cable Compatible standards IEEE 802 3ab IEEE 802 3an To avoid interference between cables layer cables as follows Use category 6A or above cables and connectors Do not bundle cables in their...

Страница 59: ...Gbps Flashing green The port is sending or receiving data at 10 Gbps Steady yellow A transceiver module or cable has been correctly installed The port has a link and is operating at 1 Gbps Flashing ye...

Страница 60: ...see Table8 21 Table8 20 Copper management Ethernet port LED description LED mark Status Description LINK ACT Steady green The port is operating at 10 100 1000 Mbps and a link is present Flashing green...

Страница 61: ...when you plan the installation site for the switch Table9 1 Cooling system for the switch Available fan trays Airflow direction LSPM1FANSA From the power supply side to the port side LSPM1FANSB From t...

Отзывы: