21
Connecting the RPS1600-A to a PD
Connecting the cables
Follow these steps to connect the RPS1600-A to a PD:
1.
Check that the power source to the RPS1600-A is disconnected
and the PD is powered off.
2.
Check that the chassis of the RPS1600-A and PD are properly
grounded.
3.
Plug one end of the DC output power cable into the DC input
socket of the PD and the other end into the DC output socket of
the RPS1600-A. Make sure the correct DC output interface and
output cable are selected.
4.
Connect the power source to the RPS1600-A and power on the
PD.
WARNING!
•
No DC output cable is supplied with the RPS1600-A. You
need to purchase one based on the PD model.
•
Check that the AC input and DC output cables are firmly
connected to eliminate poor or loose contact.
Commissioning the RPS1600-A
•
Before powering on the RPS1600-A, check the AC input with a
multimeter set to Ohms to eliminate any short circuit.
•
Upon powering on the RPS1600-A, if the run LED is on, and the
alarm LED and fault LED is off, the output is normal; if the alarm
LED or fault LED on the front panel is on, the RPS1600-A works
abnormally; if none of the run LED, alarm LED, and fault LED is
on, an AC mains problem has occurred.