5
{
When one mains power input is provided, you can configure
the power modules in N+1 or N+N redundancy. N+1 or N+N
must be not greater than the total number of power module
slots.
•
For easy usage and maintenance, configure a circuit breaker for
each power input. The rated current of the circuit breaker must
be a minimum of 120 A.