STEP 3 WIRING THE EMERGENCY BALLAST
> According
wiring diagram to connect the emergency driver to the AC driver and LED load.
Make sure all connections are in accordance with the National Electrical Code and any local regulations.
> After installation is complete, supply AC power to the emergency
driver
and join the converter connector.
> At this point, power should be connected to both the A
C
driver and the emergency
driver
, and the Charging
Indicator Light should illuminate indicating the battery is charging.
Install
and
w
ire the test switch per wiring diagrams provided on these instructions.
indicating that the emergency inverter battery is charging.
STEP 2 INSTALLING
TEST
SWITCH
Mount the supplied illuminated test switch in a location that is visible and
accessible by maintenance personnel. The
test
switch
mounts through a
0
.
49
” hole which may need to be made in the luminaire or could come
pre-punched by the luminaire supplier.
Hex Nut
Illuminated
Test Switch
Fixture Plate
Drill or Punch
a 0.49” Hole
Page
3
of
4
A
.
Test
switch
install
on
switch
box
,
switch
box
install
on
wall
or
ceiling
surface
.
T
O
TEST
C
HARGE
> A short-term discharge test may be conducted after the emergency driver has been charged for one hour. Charge
for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
> In a readily visible location, attach the label
"CAUTION - This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency
Power Supplies Before Servicing."
Page
4
of
4
Manual Operation
Auto Test Option
1. When AC power is supplied to fixture, the unit will automatically initiate a Auto test and self-diagnostic
test as follows:
(1) Verifies battery disconnection, charger board failure at every 5 seconds.
(2) 1 minute Auto testing every month.
(3) 30 minutes Auto testing on every 6 months after installation.
(4) 90 minutes Auto testing on every 12 months after installation.
2. Dual color LED lamp indicator shows the following status:
(1) Green color On / Ready
blinking: Testing
(2) Red color (Service Alert)
(3) Service Alert LED Code (Red color LED lamp indicator)
One blink, 4 second pause
Battery is not connected
Two blinks, 4 second pause
Battery voltage too low
Three blinks, 4 second pause
Four blinks, 4 second pause
Five blinks, 4 second pause
LED load not connected or failure
NOTICE
After solving the fault of emergency equipment, please press test button for 2 seconds without
releasing to reset. LED indicator will show green.
3. AUTO test also have manual test function, press test button as follows:
Press test button once
30 seconds discharge test
Press test button twice within 2 seconds
3 minutes discharge test
Press test button 3 times within 2 seconds
30 minutes discharge test
Press test button 4 times within 2 seconds
90 minutes discharge test
Ma
intenance
>
Mounting Height: This product meets or exceeds the NFPA minimum light requirements with all loads,
end use verification is necessary. For field
installations, when the attached luminaire is mounted at
down to the
smallest rated lamp load,
at
heights
up
to
7
.
17ft
(
2
.
2m
).
Many
factors
influence
emergency
illumination levels, such as the lamp load selected, luminare design, and environmental factors therefore
heights greater than 7.17ft (2.2m), the level of illumination
must be measured in the end application to
ensure the requirements of NFPA 101 and local codes are satisfied.
P
USH
NOTE: Switch
box
no
provide
.
ST:
MT:
Auto test
Manual test
NOTE: Associated Target Luminaire : Jewoo CULPL66X-BC
,
Max. mounting height 21ft / 23ft / 36ft ,
Others luminaire suitable for used shall be selected according to the instruction suggestion.
(See electrical data table)
This emergency driver will operate an LED lighting load supplies
up to 7W / 12W / 25W constant power with output voltage between 50 VDC and 200 VDC in
emergency mode for minimum of 90 minutes.
(See electrical data table)
YELLOW
ORANGE
BLUE
LED LOAD
AC LED DRIVER
BLACK
WHITE
WHT/BLUE
WHT/RED
SWITCH
(OPTIONAL)
LIVE
NEUTRAL
DC+
DC-
N
L
WHT/BLK
WHT/BLK
RED
BLACK
TEST SWITCH
(double color LED)
CONVERTER
CONNECTOR
GREEN
BROWN
MT
+
-
ST
WIRING DIAGRAM FOR PARTED AC DRIVER AND LED MODULE
YELLOW
ORANGE
BLUE
AC LINEAR LED DRIVER
WITH LED LOAD
BLACK
WHITE
WHT/BLUE
WHT/RED
SWITCH
(OPTIONAL)
LIVE
NEUTRAL
N
L
WIRING DIAGRAM FOR INTEGRAL AC DRIVER AND LED MODULE
WHT/BLK
WHT/BLK
RED
BLACK
TEST SWITCH
(double color LED)
CONVERTER
CONNECTOR
GREEN
BROWN
MT
ST
Maintenance
Transfer system failure
Charger board circuit failure