STEP 3 WIRING THE EMERGENCY BALLAST

 

> According

 wiring diagram to connect the emergency driver to the AC driver  and LED load.

 Make sure all connections are in accordance with the National Electrical Code and any local regulations.

> After installation is complete, supply AC power to the emergency

driver

and join the converter connector. 

 > At this point, power should be connected to both the A

C

 driver and the emergency 

driver

, and the Charging 

 Indicator Light should illuminate indicating the battery is charging.

  

Install

 

and

 

w

ire the test switch per wiring diagrams provided on these instructions.

 indicating that the emergency inverter battery is charging. 

 

STEP 2 INSTALLING 

TEST

 

SWITCH

 

    Mount the supplied illuminated test switch in a location that is  visible and  

accessible by maintenance personnel. The 

test

 

switch

 mounts through a 

0

.

49

” hole which may need to be made in the luminaire or could come  

 pre-punched by the luminaire supplier.

 

 

 

Hex Nut

Illuminated

Test Switch

Fixture Plate

Drill or Punch

a 0.49” Hole

Page

 

3

 

of

 

4

A

Test

 

switch

 

install

 

on

 

switch

 

box

switch

 

box

 

install

 

on

 

wall

 

or

 

ceiling

 

surface

.  

T

O

 

TEST

C

HARGE

> A short-term discharge test may be conducted after the emergency driver  has been charged for one hour. Charge 

 for 24 hours before conducting a long-term discharge test. Refer to OPERATION.

> In a readily visible location, attach the label 

  "CAUTION - This Unit Has More Than One Power Connection Point. 

 To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency 

Power Supplies Before Servicing."

Page

 

4

 

of

 

4

   Manual Operation

 

 

Auto Test Option

1. When AC power is supplied to fixture, the unit will automatically initiate a Auto test and self-diagnostic  
    test as follows:

(1) Verifies battery disconnection, charger board failure at every 5 seconds. 

(2) 1 minute Auto testing every month. 
(3) 30 minutes Auto testing on every 6 months after installation. 
(4) 90 minutes Auto testing on every 12 months after installation. 

2. Dual color LED lamp indicator shows the following status: 

(1) Green  color     On / Ready 
                                 blinking:  Testing
(2)  Red color        (Service Alert)
(3)  Service Alert LED Code (Red color LED lamp indicator)  

One blink,        4 second pause 

Battery is not connected 

Two blinks,      4 second pause 

Battery voltage too low 

Three blinks,   4 second pause 

Four blinks,     4 second pause 

Five blinks,  4 second pause 

LED load not connected or failure

NOTICE

 

After solving the fault of emergency equipment, please press test button for 2 seconds without 
releasing to reset. LED indicator will show green.

3. AUTO test also have manual test function, press test button as follows: 

Press test button once 

30 seconds discharge test 

Press test button twice within 2 seconds  

3 minutes discharge test 

Press test button 3 times within 2 seconds 

30 minutes discharge test

Press test button 4 times within 2 seconds  

90 minutes discharge test

   Ma

intenance

 

 

 

>  

Mounting Height: This product meets or exceeds the NFPA minimum light requirements with all loads,   

end use verification is necessary. For field

installations, when the attached luminaire is mounted at   

down to the 

smallest rated lamp load,

 

at

 

heights

 

up

 

to

 

7

.

17ft

 (

2

.

2m

). 

Many

 

factors

 

influence

 

emergency  

illumination levels, such as the lamp load selected, luminare design, and environmental factors therefore 

 heights greater than 7.17ft (2.2m), the level of illumination 

must be measured in the end application to 

  ensure the requirements of NFPA 101 and local codes are satisfied.

   

P

USH

NOTE: Switch

 

box

 

no

 

provide

 

 

ST:

MT: 

 Auto test        

Manual test

  NOTE: Associated Target Luminaire : Jewoo CULPL66X-BC

Max. mounting height 21ft / 23ft / 36ft ,

Others luminaire suitable for used shall be selected according to the instruction suggestion.

  

(See electrical data table)

 This emergency driver will operate an LED lighting load supplies 

up to 7W / 12W / 25W constant power with output voltage between 50 VDC and 200 VDC in 
emergency mode for minimum of 90 minutes.

(See electrical data table)

YELLOW

ORANGE

BLUE

LED LOAD

AC LED DRIVER

BLACK

WHITE

WHT/BLUE

WHT/RED

  SWITCH 
 (OPTIONAL)

LIVE

NEUTRAL 

DC+

DC-

N

L

WHT/BLK

WHT/BLK

RED

BLACK

 TEST SWITCH
 (double color LED)

CONVERTER
CONNECTOR

GREEN

BROWN

MT 

+

-

ST 

WIRING DIAGRAM FOR PARTED AC DRIVER AND LED MODULE

YELLOW

ORANGE

BLUE

AC  LINEAR LED DRIVER

WITH LED LOAD

BLACK

WHITE

WHT/BLUE

WHT/RED

  SWITCH 
 (OPTIONAL)

LIVE

NEUTRAL 

N

L

WIRING DIAGRAM FOR INTEGRAL AC DRIVER AND LED MODULE

WHT/BLK

WHT/BLK

RED

BLACK

 TEST SWITCH
 (double color LED)

CONVERTER
CONNECTOR

GREEN

BROWN

MT 

ST 

 

Maintenance

Transfer system failure

Charger board circuit failure