GWAN HSIAN ELECTRIC&MACHINERY CO.,LTD
69
Sn-45
~
Sn-61
:
Auto_Run mode selection
Name
Settin
g
Function
Factory
Setting
Description
0
Auto_Run Mode not
effective
1
Auto-Run mode for one
single cycle.
(continuing running from
the unfinished step if
restarting)
2
Periodic running
Auto_Run Mode
(continue running from
the unfinished step if
restarting)
3
Auto-Run mode for one
single cycle,then hold the
speed of final step to run
(continuing running from
the unfinished step if
restarting)
4
Auto-Run mode for one
single cycle from the firs
step.(starting a new cycle
if restarting)
5
Auto-Run mode
performed periodically
from first step.
(starting a new cycle if
restarting)
Sn-45
Auto_
Run
Mode
selection
6
Auto-Run mode for one
single cycle, then hold the
speed of final step to run
(starting a new cycle if
restarting)
0
0 STOP
1 Forward
Sn-46
~
Sn-61
Auto_
Run
Mode
selection
2 Reverse
0
1. Auo-Run mode can provide up yo 16 step settings
for simplified PLC operation. Among them, every
step setting has its different frequency
command(by An-01~16), Auto-Run mode
selection(Sn-46~61) and operation
time(Bn-22~37) for many different combinations
2. The multi-step frequency command 1~4 derived
from the multi-function input terminals
~
are ineffective.(refer to Sn-25~28)
~
3. ACC/DEC time follow the setting of Bn-01,
Bn-02 in Auto_Run Mode.
4. If the setting values of Bn-22~Bn-37 are all zero,
the Auto_Run mode is disabled
5. ACC/DEC time follow the setting of
Bn-01,Bn-02
6. Sn-45=1~3: If the inverter stops and starts again,
it will continue running from the unfinished step,
according to the setting of Sn-45
Sn-45=4~6:If the inverter stops and starts again,it
will begin a new cycle and conitinue running
according to the setting of Sn-44
7. Samples of each Auto_Run Mode are as
followings: