GWAN HSIAN ELECTRIC&MACHINERY CO., LTD
26
bn-05
~
bn-10:Analog output setting
Parameter No. &
Name
Setting Range
Unit
Factory
Setting
Function
bn-05
Analog
frequency
command VIN
Gain
0.0
~
1000.0
%
0.1
%
100.0
%
bn-06
Analog
frequency
command VIN
Bias
-100.0
~
100.0
%
0.1
%
0.0
%
bn-07
Analog
frequency
command AIN
Gain
0.0
~
1000.0
%
0.1
%
100.0
%
bn-08
Analog
frequency
command AIN
Bias
-100.0
~
100.0
%
0.1
%
0.0
%
bn-09
Multi-function
Analog Input
AUX Gain
0.0
~
1000.0
%
0.1
%
100.0
%
bn-10
Multi-function
Analog Input
AUX Bias
-100.0
~
100.0
%
0.1
%
0.0
%
Analog voltage frequency command VIN gain
:
Input voltage
range:0
~
10V
,
Analog current frequency command AIN gain
:
Input current
range:4
~
20mA
,
Multi-function analog input AUX gain
:
Input voltage range:0
~
10V
,
Analog voltage frequency command VIN bias
:
Input voltage
range:0
~
10V
,
Analog current frequency command AIN bias
:
Input current
range:4
~
20mA
,
Multi-function analog input AUX bias
:
Input voltage range:0
~
10V
,
For every different Analog Frequency Command (Voltage or
Current) and Multi-Function Analog Inputs, their
corresponding Gain and Bias are related as Fig 5.
Command Value
Input Voltage
(Input Current)
* ( ) If current
command is used
0V
(4mA)
10V
(20mA)
Max. Output
Frequency
100
Bias
Max. Output
Frequency
100
Gain
Fig .5 Analog input gain and bias