83
Expert Power Control 1202/1292
© 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
Request Code
1 Byte
0x01
Starting Address
2 Bytes
0x000 to 0x3ff
Quantity of coils
2 Bytes
1 to 0x400
Response Code
1 Byte
0x01
Byte count
1 Byte
n
Coil Status
n Byte
each Bit represents a state
·
Read Discrete Inputs (0x02)
Reads state informations:
Request Code
1 Byte
0x02
Starting Address
2 Bytes
0x400 to 0x7ff
Quantity of Inputs
2 Bytes
1 to 0x400
Response Code
1 Byte
0x02
Byte count
1 Byte
n
Input Status
n Byte
each Bit represents a state
Address
Information
0x400 to 0x7ff
State of passive device Inputs
0x800
Stop Condition active (ENC 2302)
0x801
POE active
0x1000 to 0x100f
State of Power Sources
·
Write Single Coil (0x05)
Sets the state of a port (relay):
Request Code
1 Byte
0x05
Output Address
2 Bytes
0x00 to 0x3ff
Output Value
2 Bytes
0x0000 or 0xff00
Response Code
1 Byte
0x05
Output Address
2 Bytes
n
·
Write Multiple Coils (0x0F)
Sets the state of several ports (relays):
Request Code
1 Byte
0x0f
Starting Address
2 Bytes
0x00 to 0x3ff
Quantity of Outputs
2 Bytes
1 to 0x400
Byte count
1 Byte
n
Outputs Value
n x 1 Byte
each Bit represents a state
Response Code
1 Byte
0x0f
Starting Address
2 Bytes
0x00 to 0x3ff
Содержание Expert Power Control 1202
Страница 2: ...2 Expert Power Control 1202 1292 2018 Gude Analog und Digitalsysteme GmbH...
Страница 6: ...Device Description...
Страница 14: ...Operating...
Страница 36: ...Configuration...
Страница 56: ...Specifications...
Страница 88: ...Support...