49
Expert Sensor Box 7213/7214
© 2022 GUDE Systems GmbH
Configuration
Actions during configuration, device start or plugging in the sensor (for given example):
actual temperature
during configuration
actions
70 °C
Port 1 Off (above max) + Port 2 On (above min)
45 °C
Port 1 On (below max) + Port 2 On (above min)
20 °C
Port 1 On (below max) + Port 2 Off (below min)
Action matrix during operation when limit values are exceeded (for given example):
to "above max" to "below max" to "above min" to "below min"
from "above max"
-
P1 On
P1 On
P1 On + P2 Off
from "below max"
P1 Off
-
-
P2 Off
from "above min"
P1 Off
-
-
P2 Off
from "below min"
P1 Off + P2 On
P2 On
P2 On
-
Only the switching operations for which actions have been defined, are triggered. If
no "On" or "Off" action is defined for a port, the port can never reach this state by ex-
ceeding sensor values. Unless it is the initial state.
3.7
Enable E-Mail: Activates the E-Mail dispatch of messages.
Sender address: The E-Mail address of the sender.
Содержание Expert Sensor Box 7213
Страница 2: ...2 Expert Sensor Box 7213 7214 2022 GUDESystems GmbH...
Страница 5: ...Device Description...
Страница 13: ...Operating...
Страница 23: ...Configuration...
Страница 51: ...Specifications...
Страница 94: ...Support...
Страница 100: ...100 Expert Sensor Box 7213 7214 2022 GUDESystems GmbH Expert Sensor Box 7213 7214 2022 GUDE Systems GmbH 3 16 2022...