82
Expert Power Control 1104 / 1105
© 2022 GUDE Systems GmbH
Specifications
snmp snmpv2 public set "{text}"
enables SNMP v3 on/off
snmp snmpv2 public show
show if SNMP v3 isenabled
snmp snmpv2 private set "{text}"
sets SNMP v2 public cummnity
snmp snmpv2 private show
show s SNMP v2 public community
snmp system {CONTACT=0|NAME=1|
LOCATION=2} set "{text}"
sets sysLocation/sysName/sysContact
snmp system {CONTACT=0|NAME=1|
LOCATION=2} show
gets sysLocation/sysName/sysContact
snmp snmpv3 enabled set {OFF=0|ON=1}
sets SNMP v2 private community
snmp snmpv3 enabled show
show s SNMP v2 private community
snmp snmpv3 username set "{text}"
sets SNMP v3 username
snmp snmpv3 username show
show s SNMP v3 username
snmp snmpv3 authalg set {NONE=0|MD5=1|
SHA1=2|SHA256=3|SHA384=4|SHA512=5}
sets SNMP v3 authentication
snmp snmpv3 authalg show
show SNMP v3 authentication algorithm
snmp snmpv3 privalg set {NONE=0|DES=1|
3DES=2|AES128=3|AES192=4|AES256=5|
AES192*=6|AES256*=7}
sets SNMP v3 privacy algorithm
snmp snmpv3 privalg show
show SNMP v3 privacy algorithm
snmp snmpv3 authpassw d set "{passw d}"
sets SNMP v3 authentication passw ord
snmp snmpv3 privpassw d set "{passw d}"
sets SNMP v3 privacy passw ord
snmp snmpv3 authpassw d hash set "{passw d}" sets SNMP v3 authentication hashed passw ord
snmp snmpv3 privpassw d hash set "{passw d}" sets SNMP v3 privacy hashed passw ord
snmp trap type set {NONE=0|V1=1|V2=2|V3=3}
sets type of SNMP traps
snmp trap type show
show SNMP trap type
snmp trap receiver {trap_num} set "{dns_name}"
sets address and port of SNMP trap receiver
{trap_num}
snmp trap receiver {trap_num} show
show address and port of SNMP trap receiver
{trap_num}
syslog
enters cmd group "syslog"
syslog enabled set {OFF=0|ON=1}
enables syslog msgs on/off
syslog enabled show
show if syslog enabled
syslog server set "{dns_name}"
sets address of syslog server
syslog server show
show s address of syslog server
system
enters cmd group "system"
system restart
restarts device
system fabsettings
restore fab settings and restart device
system bootloader
enters bootloader mode
system flushdns
flush DNS cache
system uptime
number of seconds the device is running
system name show
show s device name
system version show
show s actual firmw are version
system {SWITCH_PORT=0} events set {OFF=0|
ON=1}
enable global events
system {SWITCH_PORT=0} events show
show s if global events enabled
system {SWITCH_PORT=0} events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E
VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5,E
VT_DISPLAY=6,EVT_CONSOLE=7,EVT_MQTT=8}
"
enables different event types
system {SWITCH_PORT=0} events type show
show s w hat event types are enabled
system {SWITCH_PORT=0} events mqtt retain set
{OFF=0|ON=1}
sets mqtt retain
system {SWITCH_PORT=0} events mqtt retain
show
show s if mqtt retain set
system sensor {VSYS=0|VAUX=1|VMAIN=2|
TCPU=3} show
show s internal sensors if model supports it
timer
enters cmd group "timer"
timer enabled set {OFF=0|ON=1}
enables timer functions
timer enabled show
show s if timer a enabled
timer syslog facility set {0..23}
sets facility level for timer syslog
timer syslog facility show
show s facility level for timer syslog