59
Expert Power Control 1104 / 1105
© 2022 GUDE Systems GmbH
Specifications
Pow er Factor of Channel betw een -1.0 and 1.00
epc1105Pangle
.69.1.5.1.2.1.9.x
Integer32
RO
Phase Angle betw een Voltage and L Line Current betw een -180.0 and
180.0
epc1105Pow erApparent
.69.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Pow er
epc1105Pow erReactive
.69.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Pow er
epc1105AbsEnergyReactive
.69.1.5.1.2.1.12.x
Unsigned32
RO
Absolute Reactive Energy counter.
epc1105AbsEnergyActiveResetta
ble
.69.1.5.1.2.1.13.x
Unsigned32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all
resettable counter.r.
epc1105AbsEnergyReactiveReset
table
.69.1.5.1.2.1.14.x
Unsigned32
RO
Resettable Absolute Reactive Energy counter.
epc1105ResetTime
.69.1.5.1.2.1.15.x
Unsigned32
RO
Time in seconds since last Energy Counter reset.
epc1105Forw EnergyActive
.69.1.5.1.2.1.16.x
Unsigned32
RO
Forw ard Active Energy counter.
epc1105Forw EnergyReactive
.69.1.5.1.2.1.17.x
Unsigned32
RO
Forw ard Reactive Energy counter.
epc1105Forw EnergyActiveResett
able
.69.1.5.1.2.1.18.x
Unsigned32
RO
Resettable Forw ard Active Energy counter.
epc1105Forw EnergyReactiveRes
ettable
.69.1.5.1.2.1.19.x
Unsigned32
RO
Resettable Forw ard Reactive Energy counter.
epc1105RevEnergyActive
.69.1.5.1.2.1.20.x
Unsigned32
RO
Reverse Active Energy counter.
epc1105RevEnergyReactive
.69.1.5.1.2.1.21.x
Unsigned32
RO
Reverse Reactive Energy counter.
epc1105RevEnergyActiveResetta
ble
.69.1.5.1.2.1.22.x
Unsigned32
RO
Resettable Reverse Active Energy counter.
epc1105RevEnergyReactiveResett
able
.69.1.5.1.2.1.23.x
Unsigned32
RO
Resettable Reverse Reactive Energy counter.
epc1105LineSensorName
.69.1.5.1.2.1.100.x
OCTETS
RW
A textual string containing name of a Line Sensor
epc1105NTPTimeValid
.69.1.5.15.1.0
INTEGER
RO
Show if valid Time is received
epc1105NTPUnixTime
.69.1.5.15.2.0
Unsigned32
RO
show received NTP time as unixtime (secs since 1 January 1970)
epc1105NTPLastValidTimestamp
.69.1.5.15.3.0
Unsigned32
RO
show seconds since last valid NTP timestamp received
epc1105SensorIndex
.69.1.6.1.1.1.x
Integer32
RO
None
epc1105TempSensor
.69.1.6.1.1.2.x
Integer32
RO
actual temperature
epc1105HygroSensor
.69.1.6.1.1.3.x
Integer32
RO
actual humidity
epc1105InputSensor
.69.1.6.1.1.4.x
INTEGER
RO
logical state of input sensor
epc1105AirPressure
.69.1.6.1.1.5.x
Integer32
RO
actual air pressure
epc1105Dew Point
.69.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
epc1105Dew PointDiff
.69.1.6.1.1.7.x
Integer32
RO
difference betw een dew point and actual temperature (Temp -
Dew Point)
epc1105ExtSensorName
.69.1.6.1.1.32.x
OCTETS
RW
A textual string containing name of a external Sensor
Содержание Expert Power Control 1104