75
Expert Net Control 2304
© 2022 GUDE Systems GmbH
Specifications
system beeper manual set {OFF=0|ON=1}
{millisec}
manually sets beeper w ith optional duration
system beeper manual show
show s beeper state
system restart
restarts device
system fabsettings
restore fab settings and restart device
system bootloader
enters bootloader mode
system flushdns
flush DNS cache
system uptime
number of seconds the device is running
system name show
show s device name
system version show
show s actual firmw are version
system display {disp_num} default extsensor
{port_num} {sen_type} set {sen_field}
show s external sensor
system display {disp_num} default set
{BLANK=0,LOCAL_TIME=1,UTC_TIME=2}
show s other contents
system display {disp_num} default show
show s default setting for display
system display default hash set "{data}"
sets hashed display setting
system display default hash show
show s hashed display setting
system {SWITCH_PORT=0} events set {OFF=0|
ON=1}
enable global events
system {SWITCH_PORT=0} events show
show s if global events enabled
system {SWITCH_PORT=0} events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E
VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5,E
VT_DISPLAY=6,EVT_CONSOLE=7,EVT_MQTT=8}
"
enables different event types
system {SWITCH_PORT=0} events type show
show s w hat event types are enabled
system {SWITCH_PORT=0} events mqtt retain set
{OFF=0|ON=1}
sets mqtt retain
system {SWITCH_PORT=0} events mqtt retain
show
show s if mqtt retain set
system panel enabled set {OFF=0|ON=1}
blocks panel buttons w hen not enabled
system panel enabled show
show s if panel buttons are enabled
system panel port all set {OFF=0|ON=1}
enable siw tch all relays from panel buttons
system panel port all show
show s if siw tch all relays from panel buttons
enabled
system sensor {VSYS=0|VAUX=1|VMAIN=2|
TCPU=3} show
show s internal sensors if model supports it
timer
enters cmd group "timer"
timer enabled set {OFF=0|ON=1}
enables timer functions
timer enabled show
show s if timer a enabled
timer syslog facility set {0..23}
sets facility level for timer syslog
timer syslog facility show
show s facility level for timer syslog
timer syslog verbose set {0..7}
sets verbose level for timer syslog
timer syslog verbose show
show s verbose level for timer syslog
timer {rule_num} enabled set {OFF=0|ON=1}
enables rule
timer {rule_num} enabled show
show s if rule is enabled
timer {rule_num} name set "{name}"
sets name of rule
timer {rule_num} name show
show s name of rule
timer {rule_num} {FROM=0|UNTIL=1} set "{yyyy-
mm-dd}"
sets date range of rule
timer {rule_num} {FROM=0|UNTIL=1} show
show s date range of rule
timer {rule_num} trigger jitter set {0..65535}
sets jitter for rule
timer {rule_num} trigger jitter show
show jitter of rule
timer {rule_num} trigger random set {0..100}
sets probability for rule
timer {rule_num} trigger random show
show s rule probability
timer {rule_num} trigger {HOUR=0|MIN=1|SEC=2|
DAY=3|MON=4|DOW=5} set "{time_date_list}"
sets time date list
timer {rule_num} trigger {HOUR=0|MIN=1|SEC=2|
DAY=3|MON=4|DOW=5} show
show s time date list
timer {rule_num} action mode set {SWITCH=1|
CLI=2}
sets sw itch or cli cmd
timer {rule_num} action mode show
show s if sw itch or cli cmd
timer {rule_num} action {SWITCH1=0|SWITCH2=1}
{OFF=0|ON=1} set "{port_list}"
sets port list for sw itch cmd
Содержание Expert Net Control 2304
Страница 1: ...Manual Expert Net Control 2304 2022 GUDE Systems GmbH Manual Ver 1 0 1 from Firmware Ver 1 0 ...
Страница 2: ...2 Expert Net Control 2304 2022 GUDESystems GmbH ...
Страница 5: ...Device Description ...
Страница 12: ...Operating ...
Страница 23: ...Configuration ...
Страница 52: ...Specifications ...
Страница 87: ...Support ...
Страница 93: ...93 Expert Net Control 2304 2022 GUDESystems GmbH Expert Net Control 2304 2022 GUDE Systems GmbH 3 16 2022 ...