Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).

6

Guardian Equipment 
1140 N North Branch St 
Chicago, IL 60642

312 447 8100 

telephone

 

312 447 8101 

facsimile 

gesafety.com

rev. 1215 / © 2015  Guardian Equipment

Installation, Operation and Maintenance Guide

G3600LF Series Thermostatic Mixing Valves

Flow Capacities

System Pressure Drop (PSI)

0

12.5

25

37.5

50

Flow Rate (GPM)

1

2

3

4

5

6

7

8

9

10

Limited Warranty

Guardian Equipment warrants the original purchaser that its products will be free from defects in materials and workmanship under normal usage conditions, 

and when properly installed and maintained according to manufacturer's instructions for a period of two years from date of shipment. During the warranty 

period, Guardian Equipment will (at its discretion) repair or replace any product or part thereof, which shall be returned, freight prepaid to Guardian's factory 

and determined by the manufacturer to be defective in materials or workmanship. There are no warranties, expressed or implied, which extend beyond verbiage 

contained herein. There are no implied warranties of merchantability or fitness for a particular purpose. Guardian Equipment will not be held liable for labor, 

incidental or consequential damages. Any alteration or improper installation or improper use of the product will void this limited warranty.

MODEL

IN

OUT

MINIMUM 

FLOW 

(GPM)

INTERNAL 

COLD WATER 

BYPASS 

MINIMUM

SYSTEM PRESSURE DROP

5

10

15

20

25

30

35

40

45

PSI

L/MIN

0.3

0.7

1.0

1.4

1.7

2.1

2.4

2.8

3.1

BAR

G3600LF 1/2"

1/2"

2

4

2.0

2.7

3.5

4.5

5.5

6.5

7.5

8.5

9.0

GPM

7.6

15

7.6

10

13

17

21

25

28

32

34

L/MIN

MAXIMUM FLOW CAPACITY

G3600LF HAS 1/2" NOMINAL SWEAT CONNECTIONS. 

G3600LF

CAUTION: ALL THERMOSTATIC MIXING VALVES HAVE 

LIMITATIONS. THEY WILL NOT PROVIDE THE DESIRED 

ACCURACY OUTSIDE OF THEIR FLOW CAPACITY 

RANGE. CONSULT CAPACITY CHART AND DO NOT 

OVERSIZE. MINIMUM FLOW MUST BE NO LESS THAN 

SHOWN ABOVE.

IMPORTANT: THESE SYSTEMS ARE DESIGNED TO 

PROVIDE MIXED WATER FROM 60 TO 90°F (15 TO 

32°C) FOR EYE OR EYE/FACE WASH APPLICATIONS 

ONLY IN ACCORDANCE WITH ASSE 1071.

Содержание G3600LF Series

Страница 1: ...eaned adjusted or repaired 2 Inlets are clearly marked on valve body casting Connect hot water to inlet marked HOT and cold water to inlet marked COLD 3 Included angle checkstops must be installed on both supply lines see above 4 Use solder or pipe cement sparingly Flush supply pipes before connecting valve Flush outlet pipe and valve once valve is connected Maximum operating pressure is 125 PSI 8...

Страница 2: ... Reset Adjustable High Temperature Limit Stop If installed on a circulated hot water system verify the valve is piped according to Required Piping Method on page 3 See page 5 for complete parts breakdown and parts kits WARNING THIS THERMOSTATIC MIXING VALVE HAS AN ADJUSTABLE HIGH TEMPERATURE LIMIT STOP WHICH MUST BE CHECKED IF TEMPERATURE IS TOO HIGH THE INSTALLER MUST RESET THIS STOP IMMEDIATELY ...

Страница 3: ...e that is a substantial distance from the hot water source Recommended hot water inlet temperature is 135 F 57 C This unit must be cycled each time the emergency equipment is inspected See ANSI Z358 1 Maintenance and Training section 1 Set the thermostatic mixing valve to full hot 2 Activate eye or eye face wash and verify outlet temperature does not exceed 90 F 32 C 3 Turn thermostatic valve to f...

Страница 4: ... long slot end nearest port sleeve nut Tighten port sleeve nut to complete reassembly DO NOT OVERTIGHTEN To Clean Thermostat Group Loosen set screw and remove handle Figure 1 Remove retaining ring and stop Push rod through cover to remove thermostat group DO NOT PULL COILS OUT OF SHAPE Use brush and cleaning solution non corrosive and grit free to remove any depost build up from thermostat coil Wa...

Страница 5: ... high temperature limit stop must be reset see page 2 2 G3600LF valves are furnished with lockable dials Includes parts to repair both hot and cold checkstops Set Screw Thermostatic Mixing Valve Parts Item Part Number Description 1 TA 5 Base Stud 2 MU 2C Cover Screw 3 6810 Thermostat Group 4 6820 Stop 5 68240 Handle 6 MU 5A Stem O Ring 7 3009 Cover O Ring 8 TAG 1M Port Sleeve Assembly Item Part Nu...

Страница 6: ...d determined by the manufacturer to be defective in materials or workmanship There are no warranties expressed or implied which extend beyond verbiage contained herein There are no implied warranties of merchantability or fitness for a particular purpose Guardian Equipment will not be held liable for labor incidental or consequential damages Any alteration or improper installation or improper use ...

Отзывы: