background image

Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).

5

Guardian Equipment 
1140 N North Branch St 
Chicago, IL 60642

312 447 8100 

telephone

 

312 447 8101 

facsimile 

gesafety.com

rev. 1215 / © 2015  Guardian Equipment

Installation, Operation and Maintenance Guide

G3600LF Series Thermostatic Mixing Valves

11

12

13

15

14

16

RK3600B

 

Repair Kit*

RK3600A

 

Repair Kit

Notes:

1. After installing new parts, the adjustable high 

temperature limit stop must be reset (see page 2).

2. G3600LF valves are furnished with lockable dials.

* Includes parts to repair both hot and cold checkstops

Set Screw

Thermostatic Mixing Valve Parts

Item Part Number

Description

1

TA-5

Base Stud

2

MU-2C

Cover Screw

3

6810

Thermostat Group

4

6820

Stop

5

68240

Handle

6

MU-5A

Stem O-Ring

7

3009

Cover O-Ring

8

TAG-1M

Port Sleeve Assembly

Item Part Number

Description

9

6806

Cover Gasket

10

3402

Port Sleeve Nut

11

LVC-8A

Check Bonnet Packing

12

MU-6A

Lower Stem with Packing

13

MU-9A

Check Spring

14

MU-5A

O-Ring

15

MU-4A

Upper Check Stem

16

192700

Check Bonnet

1

9

7

8

10

2

4

5

3

6

7

6

9

10

8

Checkstop Parts

Thermostat Group

Lockable Dial

Содержание G3600LF Series

Страница 1: ...eaned adjusted or repaired 2 Inlets are clearly marked on valve body casting Connect hot water to inlet marked HOT and cold water to inlet marked COLD 3 Included angle checkstops must be installed on both supply lines see above 4 Use solder or pipe cement sparingly Flush supply pipes before connecting valve Flush outlet pipe and valve once valve is connected Maximum operating pressure is 125 PSI 8...

Страница 2: ... Reset Adjustable High Temperature Limit Stop If installed on a circulated hot water system verify the valve is piped according to Required Piping Method on page 3 See page 5 for complete parts breakdown and parts kits WARNING THIS THERMOSTATIC MIXING VALVE HAS AN ADJUSTABLE HIGH TEMPERATURE LIMIT STOP WHICH MUST BE CHECKED IF TEMPERATURE IS TOO HIGH THE INSTALLER MUST RESET THIS STOP IMMEDIATELY ...

Страница 3: ...e that is a substantial distance from the hot water source Recommended hot water inlet temperature is 135 F 57 C This unit must be cycled each time the emergency equipment is inspected See ANSI Z358 1 Maintenance and Training section 1 Set the thermostatic mixing valve to full hot 2 Activate eye or eye face wash and verify outlet temperature does not exceed 90 F 32 C 3 Turn thermostatic valve to f...

Страница 4: ... long slot end nearest port sleeve nut Tighten port sleeve nut to complete reassembly DO NOT OVERTIGHTEN To Clean Thermostat Group Loosen set screw and remove handle Figure 1 Remove retaining ring and stop Push rod through cover to remove thermostat group DO NOT PULL COILS OUT OF SHAPE Use brush and cleaning solution non corrosive and grit free to remove any depost build up from thermostat coil Wa...

Страница 5: ... high temperature limit stop must be reset see page 2 2 G3600LF valves are furnished with lockable dials Includes parts to repair both hot and cold checkstops Set Screw Thermostatic Mixing Valve Parts Item Part Number Description 1 TA 5 Base Stud 2 MU 2C Cover Screw 3 6810 Thermostat Group 4 6820 Stop 5 68240 Handle 6 MU 5A Stem O Ring 7 3009 Cover O Ring 8 TAG 1M Port Sleeve Assembly Item Part Nu...

Страница 6: ...d determined by the manufacturer to be defective in materials or workmanship There are no warranties expressed or implied which extend beyond verbiage contained herein There are no implied warranties of merchantability or fitness for a particular purpose Guardian Equipment will not be held liable for labor incidental or consequential damages Any alteration or improper installation or improper use ...