Installation, Operation and Maintenance Guide

G3600 Series Thermostatic Mixing Valves

Flow Capacities

Maximum flow capacity gallons per minute

Pr

essure drop PSIG

CAUTION: ALL THERMOSTATIC WATER MIXING 

VALVES HAVE LIMITATIONS. THEY WILL NOT PROVIDE 

THE DESIRED ACCURACY OUTSIDE OF THEIR FLOW 

CAPACITY RANGE. CONSULT THE CAPACITY CHART 

AND DO NOT OVERSIZE. MINIMUM FLOW MUST BE 

NO LESS THAN SHOWN BELOW.

IMPORTANT: THESE SYSTEMS ARE DESIGNED TO 

PROVIDE MIXED WATER FROM 60 TO 90°F (15 TO 

32°C) FOR FACE/EYEWASH APPLICATIONS ONLY. CALL 

GUARDIAN EQUIPMENT FOR SYSTEMS DESIGNED 

TO OPERATE AT TEMPERATURES OUTSIDE OF THIS 

RANGE.

Limited Warranty

Guardian Equipment warrants the original purchaser that products manufactured by them, (not by others), will be free from defects in materials and 

workmanship under normal conditions of use. When properly installed and maintained in accordance with Guardian Equipment’s instructions, for a period of one 

year from date of shipment. During this period the Guardian Equipment  will at its option repair or replace any product, or part thereof, which shall be returned, 

freight prepaid, to the Guardian Equipment factory and determined by Guardian Equipment to be defective in materials or workmanship. There are no warranties, 

express or implied, which extend beyond the description contained herein. There are no implied warranties of merchantability or of fitness for a particular 

purpose. In no event will Guardian Equipment be liable for labor or incidental or consequential damages. Any alteration or improper installation or use of the 

product will void this limited warranty.

MODEL IN** OUT**

MINIMUM 

FLOW 

(GPM)

INTERNAL 

COLD WATER 

BYPASS 

MINIMUM

SYSTEM PRESSURE DROP

5

10

15

20

25

30

35

40

45

PSI

L/MIN

.3

.7

1.0

1.4

1.7

2.1

2.4

2.8

3.1

BAR

G3600 1/2"

1/2"

2

4

2.5

4

5

6

7

8

8.5

9.5

10

GPM

7.6

15

9.5

15

19

23

27

30

32

36

38

L/MIN

MAXIMUM FLOW CAPACITY

**G3600 HAS 1/2" NOMINAL SWEAT CONNECTIONS.  

G3650 HAS 3/4" NPT THREADED CONNECTIONS.

G3600 
G3650

Содержание G3600 Series

Страница 1: ...lve body casting Connect the hot water into the inlet marked HOT and cold water into the inlet marked COLD 3 The checkstops furnished must be installed on both supply lines as shown above 4 Use solder or pipe cement sparingly Supply pipes should be flushed before the valve is connected Flush outlet pipe and valve as soon as it is connected Maximum Operating Pressure 125PSI 860 KPA for Hot and Cold...

Страница 2: ...LETE PARTS BREAKDOWN AND PARTS KITS If installed on a circulated hot water system make certain the valve is piped according to Guardian Equipment Required Methods of Piping see page 3 WARNING THIS THERMOSTATIC MIXING VALVE HAS AN ADJUSTABLE HIGH TEMPERATURE LIMIT STOP WHICH MUST BE CHECKED IF TEMPERATURE IS TOO HIGH THE INSTALLER MUST RESET THIS STOP IMMEDIATELY ALWAYS CHECK THE TEMPERATURE OF THE...

Страница 3: ...d check to be sure outlet temperature does not climb above 90 F 32 C Turn primary thermostatic valve to full cold and wait ten seconds Turn primary thermostatic valve to full hot and wait ten seconds Check to be sure outlet temperature does not climb above 90 F 32 C Turn primary thermostatic mixing valve to full cold and wait ten seconds Set primary thermostatic mixing valve to the desired tempera...

Страница 4: ...ts facing directly toward front of the valve Tighten port sleeve nut 3402 just enough to hold port sleeve in place do not cramp or dis tort port sleeve by exerting excess size pressure when tighten ing port sleeve nut To Clean Thermostat Group To clean thermostat group 6810 DWG 1 remove handle 68240 by loosening lock screw and pull off Remove stop re taining ring MU 13D and stop 6820 Remove thermo...

Страница 5: ...U 5A RK3600B LVC 8A CHECK BONNET B21202 LOWER STEM AND PACKING B05153 SPRING B21204 UPPER STEM B21205 WASHER B21206 PACKING B21207 BONNET NUT MU 6A LOWER STEM w PKG MU 9A CHECK SPRING MU 4A UPPER CHECK STEM LVC 7A CHECK BONNET MU 5A O RING RK3650B RK3600A STEM 0 RING MU 5A 2 COVER O RING 3009 Note G3600 G3650 Valves are furnished with lockable pointers Checkstop Parts Repair Kit Lock Type Pointer ...

Страница 6: ...free from defects in materials and workmanship under normal conditions of use When properly installed and maintained in accordance with Guardian Equipment s instructions for a period of one year from date of shipment During this period the Guardian Equipment will at its option repair or replace any product or part thereof which shall be returned freight prepaid to the Guardian Equipment factory an...

Отзывы: