Page 89
Issue 05/2013
Operation
Generator operation
Generator with attached switch box
Important
Risk of damage
y
When using several devices on the AC power sockets at
the same time (especially on devices with different power
consumption ratings), temporary over and undervoltages may
arise due to a switch-on delay in the neutral conductor.
►
Do not use the line circuit breakers in the switch cabinet for
switching the connected equipment on or off.
Important
►
The cover on the switch box and the hinged covers on unused
power sockets must always be closed correctly to ensure
protection class IP54 (tighten the lock screws by hand).
NOTE
Fault current (RCD) protective circuit breakers are in principal not
fully-functional in unearthed networks (electrical separation as made
available by the generator) since the earthing is missing. A downstream
protection measure by means of a fault current protective circuit breaker
is not necessary as a result of the “electrical separation” safety measure
provided by the generator.
Put the generator into service and connect the consumers
Note
The sum of all connected extension cables must not exceed the
following lengths:
y
max. 250 m given a conductor cross section of 2.5 mm²
y
max. 100 m given a conductor cross section of 1.5 mm²