                                                                                Important Safety Instructions 

ZY120 1-3kVA User Manual EN rev.08.docx

 

1. Electromagnetic Compatibility 

 
 

* Safety

 

IEC/EN 62040-1

 

* EMI

 

Conducted Emission.........IEC/EN 62040-2

 

Class C2

 

Radiated Emission............IEC/EN 62040-2

 

Class C2

 

*EMS

 

ESD..................................IEC/EN 61000-4-2

 

Level 4

 

RS....................................IEC/EN 61000-4-3

 

Level 3

 

EFT..................................IEC/EN 61000-4-4

 

Level 4

 

SURGE............................IEC/EN 61000-4-5

 

Level 4

 

Low Frequency Signals..............:IEC/EN 61000-2-2

 

Warning: 

This is a product for commercial and industrial application in the second 

environment-installation restrictions or additional measures may be needed to 
prevent disturbances.

 

 

WARNING:

 This is a category C2 UPS product. In a residential environment, this product

 

may cause radio interference, in which case the user may be required to take additional

 

measures.

 

 

NOTICE

 

This is a product for restricted sales distribution to informed partners. Installation restrictions or 
additional measures may be needed to prevent radio interference.

 

Operated the UPS in an indoor enviroment only in an ambient temperature range of 0-40

C(32-

104

F). Install it in a clean environment, free from moisture, flammable liquids, gases and 

corrosive substance.

 

This UPS contains no user-serviceable parts except the internal battery pack. The UPS on/off 
push buttons do not electrically isolate internal parts. Under no circumstance attempt to gain 
access internally, due to the risk of electric shock or burn.

 

Do not continue to use the UPS if the panel indications are not in accordance with these operating 
instructions or the UPS performance alters in use. Refer all fault to your dealer.

 

Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries 
and the precautions. Keep unauthorized personnel away from the batteries. Proper disposal of 
batteries is required. Refer to your local laws and regulations for disposal requirement.

 

Содержание ZY120

Страница 1: ...Uninterruptible Power Supply ZY120 1 3kVA User Manual...

Страница 2: ...Important Safety Instructions 2 ZY120 1 3kVA User Manual EN rev 08 docx EMPTY PAGE...

Страница 3: ...gh short circuit current Following precautions should be observed before replacing the battery Wear rubber gloves and boots Remove rings watches and other metal objects Use tools with insulated handle...

Страница 4: ...e The product s components must be disposed of separately as a WEEE Any violations are punishable in accordance with the current regulations Improper disposal of the product or the improper use of the...

Страница 5: ...Battery Charger 11 3 5 DC to DC Converter 12 3 6 Battery 12 3 7 Dynamic Bypass 12 4 Product Specification and performance 12 4 1 Model Description 12 4 2 Product Specification and Performance 12 5 In...

Страница 6: ...l EN rev 08 docx 9 1 Battery Disposal 21 9 2 Battery Replacement Procedures 22 10 Trouble shooting 22 10 1 Checking UPS status 22 10 2 Adjust the factors caused the problem 23 Annex A Intelligent Slot...

Страница 7: ...ed partners Installation restrictions or additional measures may be needed to prevent radio interference Operated the UPS in an indoor enviroment only in an ambient temperature range of 0 40 C 32 104...

Страница 8: ...t is designed to provide conditioned power to microcomputers and other sensitive electronic equipment When it is generated alternating current is clean and stable However during transmission and distr...

Страница 9: ...Important Safety Instructions 9 ZY120 1 3kVA User Manual EN rev 08 docx Fig 1 Front View 1KVA 2KVA...

Страница 10: ...232 communication port DB9 type 2 EPO Short to activate 3 Intelligent slot 4 USB port B type 5 Input surge protection slot 6 Input socket 1KVA IEC C14 2K 3K IEC C20 7 Network surge protection 8 Outpu...

Страница 11: ...uring that the waveform of the input current used by the UPS is near ideal Extracting this sinewave input current achieves two objects The utility power is used as efficiency as possible by the UPS Th...

Страница 12: ...event of a UPS malfunction Should the UPS have an overload over temperature or any other failure condition the UPS automatically transfers the connected load to bypass Bypass operation is indicated by...

Страница 13: ...umidity Altitude Storage temperature 0 C 40 C 95 1000m 20 C 70 C NOTICE If the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated in use please...

Страница 14: ...Connect Input Output Power 5 2 1 Notes for installation 1 The UPS must be installed in a location with good ventilation far away from water inflammable gas and corrosive agents 2 Ensure the air vents...

Страница 15: ...ell for load which current is over 10A a b Fig 3 Output terminal of 3KVA 1 Remove the cover of output terminal 2 Use AWG14 wires for terminal wiring configuration as fig 3 a 3 Please check if the wire...

Страница 16: ...end of battery cable is a plug and the other end has 2 open wires 3 Connect the RED wire to the terminal of the battery Connect the BLACK wire to the terminal of the battery Notice DO NOT connect the...

Страница 17: ...NC button to transfer in different menus 2 Press FUNC button for 3 seconds to mute off 3 Press FUNC and ON OFF together for 2 5 seconds to set rated parameters when only power supply is on Indicators...

Страница 18: ...3kVA User Manual EN rev 08 docx dark battery is connected 1 2 3 4 5 Fig 6 LCD Main Menu Description of Main Menu Display Function Submenu 1 Input information Input voltage VAC Input frequency Hz Input...

Страница 19: ...3 208V 60Hz 4 220V 50Hz 5 220V 60Hz 6 230V 50Hz 7 230V 60Hz 8 240V 50Hz 9 240V 60Hz mute on mute off 3 Battery information Battery voltage VDC Capacity if needed Firmware version Battery low warn LOW...

Страница 20: ...e buzzer alarms 2 A few seconds later the UPS turns into Battery mode and inverter feeds the load 3 Turn off the UPS in normal mode 1 Press ON OFF for 2 5 seconds button in condition of normal mode 2...

Страница 21: ...ubber gloves and boots use tools with insulated handles 3 If it is necessary to replace any connection cables please purchase the original materials from the authorized distributors or service centers...

Страница 22: ...dicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem Use the following information to determine whether external factors cause...

Страница 23: ...rn Line neutral wires reversed PE not grounded Input Line and neutral is reversed Check the polarity of line wire and neutral wire PE wire is not connected correctly in UPS Check if PE on input plug i...

Страница 24: ...utility failure UPS output will be off until utility power is on Please save your data when UPS alarm utility fail 47 Fault Rectifier fault Bus over voltage bus unbalance rectifier starting failure bu...

Страница 25: ...current enter in rectifier Please contact with distributer or service center 74 Warn Manual shutdown UPS will shutdown output or transfer to bypass mode Battery discharge time diminishes The battery...

Страница 26: ...occurs Closed when mains is OK Normal mode 1 5 Opened when inverter OFF Closed when inverter ON Battery low 1 6 Opened when alarm occurs Closed without alarm General alarm 1 7 Opened when alarm occur...

Страница 27: ...ion to shutdown UPS completely at emergency condition This function can be activated through a remote contact provided by the user It requires opening NC contact For remote function is necessary to re...

Страница 28: ...y and ensure that rectifier inverter bypass and discharge are not working 2 Press ON OFF and FUNC together for 2 5 seconds to enter in setting mode all LEDs flicker 3 Voltage setting press FUNC to cha...

Страница 29: ...00V 60Hz 2 208V 50Hz 3 208V 60Hz 4 220V 50Hz 5 220V 60Hz 6 230V 50Hz 7 230V 60Hz 8 240V 50Hz 9 240V 60Hz Note this setting menu is available only with UPS in stand by mode Switch off the UPS before se...

Страница 30: ...t protocol INPUT OUTPUT LOAD CONVERTER BYPASS Protocol Current setting Factory setting 1cc 8 Press ON OFF to choose protocol and display current setting VAC INPUT OUTPUT LOAD MODE CONVERTER BYPASS Hz...

Страница 31: ...31 ZY120 1 3kVA User Manual EN rev 08 docx...