Quick Start 

Modular UPS  MUST400T 

 

 

 

 

 

Содержание MUST400T

Страница 1: ...Quick Start Modular UPS MUST400T...

Страница 2: ...urer approved accessories only WARNING high earth leakage current Earth connection is critical before connecting the input supply include both utility supply and battery Earth leakage current introduc...

Страница 3: ...mal manner following the recommended operating procedures in this manual Battery voltage higher than 400Vdc All the battery maintenance and servicing procedures involving internal access need special...

Страница 4: ...xceed 400Vdc and is potentially lethal Follow the suggested actions here below Eye protection must be worn to prevent injury from accidental electrical arcs Remove rings watches and all metal objects...

Страница 5: ...re will reduce the battery life and operation below this temperature will reduce the battery capacity If the average operating temperature of battery is increased from 20 C to 30 C then the service li...

Страница 6: ...20 C to 25 C The batteries are at maximum efficiency in this temperature range for information about the battery storage and transportation as well as the environment refer to Table 9 2 This equipmen...

Страница 7: ...power terminals inside the UPS and all service activity it is recommended to leave enough free space to enable the passage of personnel with the doors fully opened It is important to leave a distance...

Страница 8: ...Quick start_MUST400T_ENG_REV00 8 a 10 module cabinet b 6 module cabinet Fig 1 1 UPS Structure...

Страница 9: ...xing holes on both sides of the front panel of the module See fig 1 2 Fig 1 2 Power Module Installation Diagram 1 4 9 Cable Entry Cables can enter into the UPS system both from bottom and top Cable en...

Страница 10: ...e RCD device installed upstream of the input supply should be comply with Sensitive to DC unidirectional pulses class A in the network Insensitive to transient current pulses Have an average sensitivi...

Страница 11: ...ermining the size of the output and bypass neutral cable as the current circulating on the neutral cable may be greater than nominal current in the case of non linear loads which is usually 1 732 time...

Страница 12: ...ut Connections 4 For common bypass and rectifier inputs connect the AC input supply cables to the UPS bypass terminals X2 L21 L22 L23 X1 N1 Refer to Fig 4 11 and tighten the connections to 5 Nm M6 Bol...

Страница 13: ...d the critical load and tighten the terminals screws to 5Nm M6 Bolt or to 13Nm M8 Bolt or to 25Nm M10 Bolt Note ENSURE CORRECT PHASE ROTATION WARNING If the load equipment will not be ready to accept...

Страница 14: ...an die USV abschlie en Ein Differentialschutz ist ratsam Conectar el cable de tierra a el SAE Se aconseja la protecction con el interruptor diferencial Attenzione batterie interne non aprire pericolo...