Operation 

The address,  working mode and tone of the flashing 

beacon  base  can  be  programmed  using  P-9910B 

programmer in field. 

 Address Programming   

Connect the programmer with Terminal 1 and 3 of the 

flashing beacon base. Turn on the programmer, enter 

the  address  code  (1 to  242),  pressing 

Program

, the 

screen  will  show  a  P   meaning  the  address  is 

programmed.  Refer  to 

P-9910B  Hand  Held 

Programmer  Installation  and  Operation  Manual

  for 

details. 

 Setting Tone and Working Mode 

In standby state of the programmer, entering number 4, 

5  and  6  followed  by 

Clear,

  the screen  will  show  0 . 

Pressing 

Function

, the screen still shows  0 . Pressing 

3   then,  the  screen  shows  - .  Entering  the  tone 

number,    and pressing 

Program, 

P  will show on the 

screen,  meaning  the  tone  number  has  been  set. 

Pressing 

Clear

,  the  screen  shows  0 ,  further 

operation can be done.    If the tone number falls into 

the range of 1 to 16, the flashing beacon base works in 

Mode I; if the number falls into the range of 17 to 32, it 

works in Mode II; if the number falls into the range of 

33-48,  it  works  in  Mode  III.  Numbers  outside  these 

three ranges will not be accepted, in which case, the 

number will be defaulted to be  46 .   

Application Method 

  The  flashing  beacon  base  can  be  used  as  a 

detector base to mount intelligent detectors, so that 

the  detector  can carry  out  both  fire  detection  and 

alarm.

 

  It  can  also  be  directly  connected  into  fire  alarm 

system. In case of a fire alarm, it will generate the 

pre-set alarm sound.   

Caution: 

 

Please  read  this  manual  carefully  before 

operation.

 

 

DZ-03  base  should  be  used together  with  this 

product. 

 

A loop can have maximum 30 flashing beacon 

bases due to their current consumption.   

 

Please  order  the  special  top  cover  if  it s  not 

connected with fire detector.

 

 

Never try to repair it by yourself. Always contact 

your distributor in case of any trouble.

 

Specifications 

Operating Voltage 

Loop 24V (20V~28V) 

Quiescent Current 

1mA 

Alarm Current 

6mA 

Mode 

Mode I, II & III.   

Alarm tones 

Optional  16  tones.  Please 

refer to the table of tones.   

Flash indication 

Bright  red  flash,  frequency 

1Hz 

Programming 

Electronically programmed 

Code Range 

1~242   

Ingress Protection 

Rating 

IP21C 

Operating 

Temperature 

-

10 ~

+

50  

Relative Humidity 

95%, non condensing 

Material of 

Enclosure 

ABS 

Dimension 

Diameter: 152.4mm 

Height: 41.3mm (without 

cover) 

Mounting Hole 

Distance 

45mm~80mm 

Weight   

About 235g 

 
 

Table of Tones 

Accessories and Tools

 

Model 

Name 

Remark 

P-9910B 

Hand 

Held 

Programmer 

Order separately   

WEEE Information 

2012/19/EU (WEEE directive): Products 

marked  with  this  symbol  cannot  be 

disposed of as unsorted municipal waste 

in  the  European  Union.  For  proper 

recycling,  return  this  product  to  your 

local  supplier  upon  the  purchase  of 

equivalent  new  equipment,  or  dispose  of  it  at 

designated collection points.   

Limited Warranty   

GST

warrants that the product will be free from defects 

in  design,  materials  and  workmanship  during  the 

warranty period. This warranty shall not apply to any 

product that is found to have been improperly installed 

or  used  in  any  way  not  in  accordance  with  the 

instructions  supplied  with  the  product.  Anybody, 

including the agents, distributors or employees, is not 

in the position to amend the contents of this warranty. 

Please contact your local distributor  for products not 

covered by this warranty. 

THIS  PRODUCT  IS  NOT  APPROVED  TO  EN54-23 

(Beacon Functionality) AND MUST NOT BE USED AS 

A  VISUAL  ALARM  DEVICE  OR  TO  PROVIDE  A 

PRIMARY WARNING NOTIFICATION OF FIRE. 

 

Mode 

Tone Description 

Sound Level 

1m Ahead/24V 

dB  

I

II  III 

1  17  33  970Hz 

87 

2  18  34  800Hz /970Hz @ 2Hz 

88 

3  19  35  800Hz-970Hz@1Hz 

84 

4  20  36  970Hz 1s on /1s off 

86 

5  21  37  970Hz, 0.5s/630Hz, 

0.5s 

88 

6  22  38  500Hz - 1200Hz 0.5s 

on×3 / 1.5s off 

81 

7  23  39  2850Hz, 0.5s on/0.5s 

off 3/1.5s off 

86 

8  24  40  2850Hz 0.4s on/0.3s 

off 

86 

9  25  41  550Hz,0.7s/1000Hz, 

0.33s 

88 

10  26  42  1500Hz -2700Hz 

@3Hz 

83 

11  27  43  2400Hz 

76 

12  28  44  500Hz -1200Hz 

@0.33Hz 

85 

13  29  45  2400Hz -2900Hz 

@9Hz 

82 

14

*

  30  46  2400Hz -2900Hz 

@3Hz

 

 

92 

15  31  47  800Hz-970Hz@3Hz 

85 

16

*

  32  48  500Hz-1200Hz,3.75s 

on /0.25s off   

85 

Pre-alarm      800Hz 1s on/1s off 

84 

EN54 Compliant 