background image

 

30304603                                                                                                                                                                    Issue 1.03

 

fiber in the chamber. 

d) 

Put back the chamber and the top cover. 

The detector should be tested after re-installed to 
ensure normal operation.

 

Fire simulation test should be done to the detector 
at least every 6 months.

 

Specification 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Accessories and Tools   

Model 

Name 

Remarks 

P-9910B  Hand Held 

Programmer 

Order separately 

DZ-03 

Base 

Order separately 

WEEE Information 

2012/19/EU  (WEEE  directive):  Products 
marked  with  this  symbol  cannot  be 
disposed of as unsorted municipal waste 
in  the  European  Union.  For  proper 
recycling, return this product to your local 
supplier upon the purchase of equivalent 

new equipment, or dispose of it at designated collection 
points.   

Limited Warranty 

GST

  warrants  that  the  product  will  be  free  of  charge 

for  repairing  or  replacing  from  defects  in  design, 

materials and workmanship during the warranty period. 

This warranty does not cover any product that is found 

to have been improperly installed or used in any way 

not  in  accordance  with  the  instructions  supplied  with 

the 

product. 

Anybody, 

including 

the 

agents, 

distributors  or  employees,  is  not  in  the  position  to 

amend  the  contents  of  this  warranty.  Please  contact 

your  local  distributor for  products  not  covered  by this 

warranty. 

 

 

Operating Voltage 

Loop 24V (16V~28V) 

Standby Current 

0.8mA 

Alarm Current 

5.0mA   

Indicators 

Red. 

Flashes 

in 

normal 

condition.  Lights  when  fire 
reported. 

Remote  Indicator 
Output 

Directly  connect  to  remote 
indicator 

(built-in 

5.1k

Ω  

resistor  in  series.  Max.  output 
current    is  5.0mA).  Quiet  in 
normal  condition.  Lights  in 
alarming. 

Programming 
Method 

Electronically programming 

Code Range 

One address within 1

242. 

Wiring 

Non-polarized 2-core for loop. 
Polarized  2-core  for  remote 
indicator. 

Ambient 
Temperature 

-

10

℃~+

50

 

Relative Humidity 

95%, non condensing 

Ingress  Protection 
Rating 

IP23 

Material  and  Color 
of Enclosure 

ABS, white (RAL 9016) 

Dimensions 

Diameter 100mm     
Height 56mm (with base) 

Mounting 

Hole 

Distance 

45mm

75mm 

Weight 

About 120g 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532

 

[email protected]

  

www.gst.com.cn

 

 