GST-RP16 Conventional Repeater Panel

 

                       

 

 

                

Installation and Operation Manual

     

                                          

       

 

Page 4 

Table1 

Number 

Problem 

Reasons 

Repair Methods 

The device 

 be 

started up. 

a. Jumper X1 is not at  ON  

end.  

b. No 5V 

a. Put X1 to  ON . 

b. Check 7805 and its 

periphery circuit  

No self-test 

or display 

wrongly 

after 

power-on 

a. Power supply is     

abnormal. 

b. Connection with display 

panel is loose. 

c. LED is damaged. 

d. Transistor oscillator or 

main CPU damaged 

a. Check 24V power supply  

b. Check wiring 

c. Replace the LED. 

d. Check transistor oscillator or 

replace main CPU 

No dealing 

with alarm 

signals 

a. Connection loose in input 

part. 

b. Insulated optocoupler 

does not work. 

c. Output circuit is 

damaged. 

d. Transistor oscillator or 

main CPU damaged. 

a. Connect it in a right way. 

b. Replace the optocoupler. 

c. Check 74HC595 and 

ULN2003 

d. Check transistor oscillator or 

replace main CPU 

No sound 

a. Output circuit is damaged 

b. Buzzer is damaged.

 

a. Check 74HC595 and 

ULN2003 

b. Replace the buzzer.

 

VIII Cautions

 

1.  Before powering up, check all cable problems, such as short circuit, open circuit 

and wrong connections etc. 

2.  GST-RP16  is  a  precise  electronic  product  and  must  be  maintained  by  specific 

personnel. 

3.  Make record on duty. 
4.  We take the responsibility of repairing the repeater. If any problem occurs, please 

contact  us  in  time.  The  users  will  be  responsible  for  any  result  from  repairing 
GST-RP16 themselves

.

 

Содержание GST-RP16

Страница 1: ...GST RP16 Conventional Repeater Panel Installation and Operation Manual Issue 1 03 Jan 2014 ...

Страница 2: ...er Panel Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 1 V Mounting and Commission 2 VI Operations 3 VII Troubleshooting 3 VIII Cautions 4 ...

Страница 3: ...es separately 2 With two fault outputs it can show fault signals from conventional FACP 3 It is wall mounted with advantages of small dimension simple installation and operation good performance high reliability and flexible configuration etc III Technical Specifications 1 Display Capacity Maximum 16 signals 2 fault signals 2 Wiring Connect with conventional FACP by multi wire 16 for fire signals ...

Страница 4: ... state can silence the alarm sound while it gives another sound to indicate the mute state 3 Operation Principle GST RP16 is a zonal fire display panel developed with microprocessor It indicates the alarm zone with LED and audio visual signal It connects with conventional FACP with multi wire providing alarm signal after processing the data from conventional FACP V Mounting and Commission 1 Mounti...

Страница 5: ... The buzzer alarms fire After self test Power ON LED is lit other LEDs are off and the buzzer doesn t sound 4 Keep chassis well grounded to ensure stable operation VI Operations 1 Put the jumper X1 ON 2 In monitoring state only Power ON LED is lit 3 When there is a fire alarm the FIRE LED is lit and the zonal FIRE LED corresponding to conventional FACP is also lit If it is the latest fire relevant...

Страница 6: ... in input part b Insulated optocoupler does not work c Output circuit is damaged d Transistor oscillator or main CPU damaged a Connect it in a right way b Replace the optocoupler c Check 74HC595 and ULN2003 d Check transistor oscillator or replace main CPU 4 No sound a Output circuit is damaged b Buzzer is damaged a Check 74HC595 and ULN2003 b Replace the buzzer VIII Cautions 1 Before powering up ...

Отзывы: