GST-RP16 Conventional Repeater Panel
Installation and Operation Manual
Page 3
2. Terminals are shown in Fig. 4.
24V GND
FAU1
FAU2
XT1
Fig. 4
24V GND:
Connect with auxiliary power terminals
AUX -
of
conventional FACP. Other
24VDC power supply can also be used, but please make
sure that the Ground of the power supply is well connected to the - of AUX
SUPPLY (+, -) of conventional FACP.
FIRE1 FIRE16:
Connect with zonal indication terminals
Z1~Z8
of
REPEATER
OUTPUT
of conventional FACP.
FAU1 FAU2:
Connect with fault terminal
FLT
of
REPEATER OUTPUT
of
conventional FACP.
Wiring: 227 IEC 05 cables for signal input and power supply, cross section is
1.0mm
2
.
3. Commission: GST-RP16 carries out self-test when power is on and all LEDs are lit.
The buzzer alarms fire. After self-test, Power ON LED is lit, other LEDs are off, and
the buzzer doesn t sound.
4. Keep chassis well grounded to ensure stable operation.
VI Operations
1. Put the jumper X1 ON .
2. In monitoring state, only Power ON LED is lit.
3. When there is a fire alarm, the FIRE LED is lit, and the zonal FIRE LED
corresponding to conventional FACP is also lit. If it is the latest fire, relevant zonal
FIRE LED flashes every 0.25s and GST-RP16 sounds every 0.25s.
4. FAULT LED is lit when there is a fault. The buzzer provides a fault sound (0.5s on,
4.5s off) if no fire alarm comes. If a fire condition occurs, the buzzer then gives fire
alarm sound every 0.25s.
5. When MUTE is pressed, fire or fault sound will be silenced, and another sound
(0.5s on, 9.5s off) indicates the mute state. If there is a fire or fault signal again, it
will sound again.
VII Troubleshooting
Common problems and repair methods are shown in Table1 below.