GST-RP16 Conventional Repeater Panel

 

                       

 

 

                

Installation and Operation Manual

     

                                          

       

 

Page 1 

I  General 

GST-RP16  Conventional  Repeater  Panel  (hereinafter  called  GST-RP16),  the 
supporting product of a conventional fire alarm control panel  FACP , is a type of fire 
display  unit  used  in  buildings  or  fire  control  center.  When  the  conventional  FACP 
receives fire signal, it will alarm and send the signal to GST-RP16. Then the GST-RP16 
will indicate the alarm zone and sound to notice the people there to act accordingly. 
GST-RP16 is a non-addressable repeater panel matching with GST102A, GST104A, 
GST108A, and GST116A Conventional Fire Alarm Control Panel.

 

II  Features 

1.  It can indicate fire signals in 16 zones separately. 
2.  With two fault outputs, it can show fault signals from conventional FACP. 
3.  It  is  wall-mounted,  with  advantages  of  small  dimension,  simple  installation  and 
operation, good performance, high reliability, and flexible configuration etc. 

III  Technical Specifications 

1.   Display Capacity: Maximum 16 

 signals, 2 fault signals. 

2.  Wiring: Connect with conventional FACP by multi-wire (16 for fire signals and 2 for 

fault signals) and two 24VDC power wires in addition. 

3.  Operation Environment: 

Temperature: 0

+40  

Relative Humidity  95%, no condensation  

4.  Power supply with 18VDC 28VDC,

 

standby current 12mA, alarm current 60mA. 

5.  Dimension: 280mm 110mm 46mm. 

IV  Structure and Operation Principle 

1. GST-RP16 is wall-mounted. Its appearance is shown in Fig. 1. 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 1 

 

ZONE12

MUTE

ZONE14

ZONE16

ZONE 2

ZONE 4

ZONE 6

ZONE 8

ZONE10

PowerON

ZONE11

ZONE 1

ZONE 3

ZONE 5

ZONE 7

ZONE 9

FAULT

FIRE

ZONE13

ZONE15

Содержание GST-RP16

Страница 1: ...GST RP16 Conventional Repeater Panel Installation and Operation Manual Issue 1 03 Jan 2014 ...

Страница 2: ...er Panel Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 1 V Mounting and Commission 2 VI Operations 3 VII Troubleshooting 3 VIII Cautions 4 ...

Страница 3: ...es separately 2 With two fault outputs it can show fault signals from conventional FACP 3 It is wall mounted with advantages of small dimension simple installation and operation good performance high reliability and flexible configuration etc III Technical Specifications 1 Display Capacity Maximum 16 signals 2 fault signals 2 Wiring Connect with conventional FACP by multi wire 16 for fire signals ...

Страница 4: ... state can silence the alarm sound while it gives another sound to indicate the mute state 3 Operation Principle GST RP16 is a zonal fire display panel developed with microprocessor It indicates the alarm zone with LED and audio visual signal It connects with conventional FACP with multi wire providing alarm signal after processing the data from conventional FACP V Mounting and Commission 1 Mounti...

Страница 5: ... The buzzer alarms fire After self test Power ON LED is lit other LEDs are off and the buzzer doesn t sound 4 Keep chassis well grounded to ensure stable operation VI Operations 1 Put the jumper X1 ON 2 In monitoring state only Power ON LED is lit 3 When there is a fire alarm the FIRE LED is lit and the zonal FIRE LED corresponding to conventional FACP is also lit If it is the latest fire relevant...

Страница 6: ... in input part b Insulated optocoupler does not work c Output circuit is damaged d Transistor oscillator or main CPU damaged a Connect it in a right way b Replace the optocoupler c Check 74HC595 and ULN2003 d Check transistor oscillator or replace main CPU 4 No sound a Output circuit is damaged b Buzzer is damaged a Check 74HC595 and ULN2003 b Replace the buzzer VIII Cautions 1 Before powering up ...

Отзывы: