GST-RP16
Conventional Repeater Panel
Installation and Operation Manual
(Issue 1.03, Jan 2014)
Страница 1: ...GST RP16 Conventional Repeater Panel Installation and Operation Manual Issue 1 03 Jan 2014 ...
Страница 2: ...er Panel Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 1 V Mounting and Commission 2 VI Operations 3 VII Troubleshooting 3 VIII Cautions 4 ...
Страница 3: ...es separately 2 With two fault outputs it can show fault signals from conventional FACP 3 It is wall mounted with advantages of small dimension simple installation and operation good performance high reliability and flexible configuration etc III Technical Specifications 1 Display Capacity Maximum 16 signals 2 fault signals 2 Wiring Connect with conventional FACP by multi wire 16 for fire signals ...
Страница 4: ... state can silence the alarm sound while it gives another sound to indicate the mute state 3 Operation Principle GST RP16 is a zonal fire display panel developed with microprocessor It indicates the alarm zone with LED and audio visual signal It connects with conventional FACP with multi wire providing alarm signal after processing the data from conventional FACP V Mounting and Commission 1 Mounti...
Страница 5: ... The buzzer alarms fire After self test Power ON LED is lit other LEDs are off and the buzzer doesn t sound 4 Keep chassis well grounded to ensure stable operation VI Operations 1 Put the jumper X1 ON 2 In monitoring state only Power ON LED is lit 3 When there is a fire alarm the FIRE LED is lit and the zonal FIRE LED corresponding to conventional FACP is also lit If it is the latest fire relevant...
Страница 6: ... in input part b Insulated optocoupler does not work c Output circuit is damaged d Transistor oscillator or main CPU damaged a Connect it in a right way b Replace the optocoupler c Check 74HC595 and ULN2003 d Check transistor oscillator or replace main CPU 4 No sound a Output circuit is damaged b Buzzer is damaged a Check 74HC595 and ULN2003 b Replace the buzzer VIII Cautions 1 Before powering up ...