GST GST-NRP00 Скачать руководство пользователя страница 13

GST-NRP00/GST-NRP00-HU/GST-NRP00-PT

                             

Network Repeater Panel Installation and Operation Manual

    

001 0f 006 !FIRE!  05:25  // There are six devices with fire alarm signals, and this is 
the first.
Zone: 001 030MCP        // The number of zone   with fire alarm and type  and 
address of the device in fire alarm.
Device-30                // Description of device in fire alarm.

Last !Fire! Zone:003        // Zone number of the last fire alarm.
Zone3   Device-066

// Description of the device and of that zone with the last fire 

alarm. 

5.2.2

Disposal of Fire Alarm Signal  

When fire alarm occurs, first find out the location according to the information shown on 
the repeater panel and verify if there is a real fire.
If it’s a real fire, please take corresponding measures as outlined below.

Step 1:

Evacuate people.

Step 2:

Call the fire department.

Step 3:

Initiate extinguishers.

If it is a false alarm, please take the following measures.

Step 1:

Press 

SILENCE

to stop the sound.

Step 2:

Remove the causes of the false alarm.

Step 3:

Press 

RESET

to make the FACP back to the normal state. If the device still 

gives  false  alarm,  disable  it  using  a FACP  in  network  and  inform  the  installer  or 
manufacturer for repair.

5.3 Fault 

5.3.1

Fault Indication

In case of fault, the repeater panel and FACPs in network display the fault message 
simultaneously and light corresponding LED. 

Mains  fault:  If  the  AC  power  of  networked  FACPs is  down,  the  repeater  panel 
reports AC fault, and 

Lights

COMMON FAULT

and

POWER FAULT

LED.

The LCD displays “AC FAULT”.
Generates fault sound.

Battery fault: The repeater panel reports battery fault if the battery voltage is lower 
than 18.9V, and would:

Light 

COMMON FAULT

and

POWER FAULT

LED.

The LCD displays “BATTERY FAULT”.

Page 10

Содержание GST-NRP00

Страница 1: ......

Страница 2: ...pply 8 4 4 2 Connection of Communication Loop 8 Chapter 5 Display and Disposal of System Information 9 5 1 Normal Information 9 5 2 Fire Alarm 9 5 2 1 Fire Alarm Screen 9 5 2 2 Disposal of Fire Alarm...

Страница 3: ...tem Administrator Manager Password Required 20 6 4 1 Modifying System Time 21 6 4 2 Modifying Password 21 6 4 3 Network Setup 22 6 4 4 Setting Zone Start Number 23 6 4 5 Initialization of System 23 Ch...

Страница 4: ...his unit until this manual is read and understood This equipment must be installed in accordance with these instructions and the appropriate national regional and local regulations specific to the cou...

Страница 5: ...peater Panel is simple installation operation and easy maintenance It is used in fire alarm system with the following features 1 The LCD can display 8 lines in total and 18 characters each line assist...

Страница 6: ...normally and less than 500mA in fire condition Standby power consumption does not exceed 9W and maximum power consumption does not exceed 13W 2 2 Communication Loop Parameters 2 channels of RS485 inte...

Страница 7: ...oard 2 Switch board 3 LCD 4 Network board 5 Speaker 6 DC DC Power supply 7 Terminal board 3 1 1 Description of LEDs FIRE Red It illuminates when the repeater panel receives a fire alarm message from f...

Страница 8: ...DER CIRCUIT OUTPUT of FACPs in network It goes out automatically after the fault is cleared SOUNDER DISABLE Yellow It illuminates steadily after the SOUNDER CIRCUIT OUTPUT of FACPs in network is disab...

Страница 9: ...ressing it can toggle the clock display between month day mode and hour minute mode SILENCE Pressing it can silence the sounders and close the output of alarm bell EVAC Pressing this key can start all...

Страница 10: ...wer converter board switch board and network board the connection of power converter board network board and terminal board and of speaker and main board etc Please refer to Appendix 1 for the interna...

Страница 11: ...Connections of Field Devices 4 4 1 Connection of Power Supply The input power for the repeater panel is non polarized 24V which is converted to 5V by a DC DC converter module 4 4 2 Connection of Comm...

Страница 12: ...ation The normal display is shown in Fig 5 1 which means the system is in working state Then only POWER ON LED lights Fig 5 1 Fig 5 2 shows the system is in normal operation but with disabled devices...

Страница 13: ...cuate people Step 2 Call the fire department Step 3 Initiate extinguishers If it is a false alarm please take the following measures Step 1 Press SILENCE to stop the sound Step 2 Remove the causes of...

Страница 14: ...the repeater panel will then interpret it as a genuine fault and the LCD displays System fault must be reset manually System time must be reset after it s cleared You need to press RESET key to clear...

Страница 15: ...notes If it is field device fault please repair it in time You can disable it if the fault can t be cleared for some reason and enable it when the fault is removed 5 4 Rules for Message Display If th...

Страница 16: ...o modify any character Pressing TAB the highlight moves to the next position and returns to the first after the last position Wherever the cursor is Pressing ENTER key all the input data will be saved...

Страница 17: ...mation one by one by pressing and 6 2 2 2 Browsing more than one piece of message The current information is highlighted when there is more than one piece of message on the LCD You can view details of...

Страница 18: ...is displaying non disable messages The screen of loop mode is shown in Fig 6 4 and the screen for zone mode is shown in Fig 6 5 and Fig 6 6 Fig 6 4 001 of 003 Disable 12 01 There are three disabled d...

Страница 19: ...B when the screen is displaying non action messages The screen is shown in Fig 6 7 Fig 6 7 001 of 004 ACTION 12 15 There are 4 action messages in the system and this is the first time 12 15 Zone 001 0...

Страница 20: ...dged by pressing RESET key the system returns to normal display state 6 3 2 Checking All Visual and Audible Indications In normal monitoring state you can check all visual and audible indications of t...

Страница 21: ...vices with device type between 01 and 11 in Zone 1 you need to input in sequence the zone number 001 device code and device type Please note that the asterisk mark is not allowed to use for action dev...

Страница 22: ...for setting up LCD contrast as shown in Fig 6 13 In this screen and are used to adjust LCD contrast Fig 6 13 Entering 2 in the screen of Fig 6 12 will enter the screen for setting up display mode as s...

Страница 23: ...as disablement operation Fig 6 15 Entering 4 in the screen of Fig 6 12 will enter the screen for manual stop of loop devices as shown in Fig 6 16 The method for stopping a device is the same as start...

Страница 24: ...ying Password Inputting 2 on the screen in Fig 6 17 the system enters the window of password modification See Fig 6 19 Now the passwords can be modified Fig 6 19 Inputting 1 or 2 to choose password to...

Страница 25: ...ication is successful Fig 6 22 6 4 3 Network Setup Inputting 3 on the screen in Fig 6 17 the screen shown in Fig 6 23 will be displayed Fig 6 23 In the above screen You can set the repeater panel s ne...

Страница 26: ...s shown in Fig 6 25 Fig 6 25 6 4 4 Setting Zone Start Number Inputting 4 on the screen in Fig 6 17 the screen shown in Fig 6 26 will be displayed The zone start number of the FACP can be set up Fig 6...

Страница 27: ...abnormal b Loose connection with switchboard a Check the input and output of power converter board b Check the connection with switchboard 2 Cannot communicate with networked FACPs The polarity of co...

Страница 28: ...al accessories Main Board MB 010 Switch Board SB 010 LCD Screen SC 200 Network Card P 9940A Speaker SP 200 DC DC Converter PB 010 Terminal Board TB 010 5V GND XS3 XS6 XS1 XS2 XS10 XS12 XP1 5V GND CN1...

Страница 29: ...XS1 XS2 XS10 XS12 XP1 5V GND CN1 CN2 CAN_L CAN_H XT1 XS1 B1 A1 B2 A2 D2 D1 B1 A1 B2 A2 GND 24V XT1 XT2 XT3 XT14 XT15 XT16 X1 X2 X3 B A K P 9960 Optional accessories Main Board MB 010 Switch Board SB 0...

Страница 30: ...nt SounderB 12 Fire broadcast Sounder 13 Sounder strobe Flasher 14 Flasher Lift 15 Lift Damper 16 Damper FireDoor 17 Fire door AHU 18 Air Conditioner Extract 19 Smoker exhauster BMS 20 Building manage...

Страница 31: ...ce Gas Dump 46 Gas extinguisher start GasAbort 47 Gas extinguisher stop User Def 48 User defined device User Def 49 User defined device User Def 50 User defined device User Def 51 User defined device...

Страница 32: ...t a menu In information display state you can return the system to the highest level VIEW DISABLE To display the information of disabled devices MODE To set display mode LCD Contrast To set LCD contra...

Отзывы: