DI-9204Exd Digital Flame-proof Manual Call Point
Installation and Operation Manual
The Intelligent Solution
Page 4
1. Grommet 2.Armored Cable 3. Entrance Interface 4. Middle Sheath 5. Taper Washer
6. Outer Washer 7. Grommet 8. Nut 9. Flame-proof Washer 10.Sealing Filler
Fig. 4
5.1.3 Connection
There are terminals on the circuit board in the cover, as shown in Fig. 5.
K1
K2
Z3
Z4
Z2
Z1
Fig. 5
Terminal description:
Z1, Z2: In addressable mode, connecting with signal cable, polarity-insensitive. In
non-addressable mode, connecting with 24VDC, polarity-insensitive.
Z3, Z4: Junction output for input signal of Z1 and Z2.
K1, K2: Volt free normally open output terminals. When the MCP is pressed, output
contact is closed to control external devices. These two terminals are optional that can
be used or not.
Connect the cables to the terminals in sequence.
(4) Final installation
After connection, put the cover into the base, and then fasten them with M5×10
Hexagon socket countersunk head screws.
5.2 Pole-mounting
The pole-mounted MCP is shown in Fig. 6 and dimension of the pole is shown in Fig. 7.
The mounting steps is as follows:
(1)
Thread the cable through the cable outlet of the pole and the rubber washer.
(2) Install the pole on the ground using M10 anchor bolts.
(3) Screw down the cover, and lay out the cables according to the application
requirement with the same method as wall-mounting.
(4) Wire the MCP with the same method as wall-mounting.
(5) Connect the MCP base with the pole using M4X10 screw assembly.
(6) Install the MCP with the same method as wall-mounting.
Gland body
E-MAIL: [email protected]