background image

 

30307775   

         

                                                                                             

                     

  Issue 1.03

 

30°

Testing 
Area

Fig. 8

 

  When  multiple  detectors  are  connected  with  a  remote 

indicator, a diode 1N5819 should be connected to Terminal 4 
of the  orientation base in  series  before going to the  positive 
of the remote indicator. System composition is shown in Fig. 
8.   

   

Fig. 7 

Maximum  15  detectors  can  be  connected  to  the  output  of  zone 
monitor unit. In case of broken circuit or removal of any detector, 
the unit will transmit a fault message to the FACP. If and AEOL is 
connected, normal operation of other device in the system will not 
be affected. 

Testing 

Note:  Before  testing,  make  sure  the  detector  is  properly 
installed and  powered up.    Testing can  only begin  after  the 
detector  is  powered  up  for  10 
seconds.   

The  detector  must  be  tested 
after  installation  and  regular 
maintenance.  The  methods  are 
as follows: 

(1) Reed switch testing 

The  testing  area  of  the  detector 
is shown in Fig. 4.   

Approach the commission tool to 
the  testing  area  of  the  detector 
and  hold  for  several  seconds 
until the detector alarms. 

(2) Temperature test 

Approach  a heater (such  as  a hair drier) to the thermistor  of the 
detector until it alarms. 

After testing, disconnect power to the detector for over 5 seconds 
to reset it. Notify the proper authorities that the system is back to 
normal operation. 

If a detector fails in testing, clean it by the steps in 

“Maintenance”, 

and retest it. If it still fails, return it for repair.  

Maintenance 

  The detector should be installed just before commission and 

kept  well  before  installation,  taken  corresponding  measures 
for dust-proof, damp-proof and corrosion-proof. 

  The dust cover cannot be removed until the project has been 

plunged into usage.   

  Clean  the  detector  at  least  once  a  year  to  ensure  normal 

operation of the system. 

  Before cleaning, notify the proper authorities that the system 

is  undergoing  maintenance  and  will  temporarily  be  out  of 
service. Disable the zone or system undergoing maintenance 
to avoid unwanted alarms. 

  The  detector  should  be  tested  again  after  cleaning  and 

re-installing. 

  Protect the metal component on the PCB against damp and 

improper distortion. 

 

  Do fire simulation test at least once every 6 months.

 

 
 
 
 
 
 
 
 
 
 
 
 

 

Specification 

Operating Voltage 

16VDC~28VDC 

Standby Current 

60μA 

Alarm Current 

10mA

I

30mA 

Fire LED 

Red. Flashes in polling; Illuminates 
in alarming.   

Remote Indication 
Output

 

Directly connecting with remote 
indicator (built in 5k resistor in 
series, maximum output current is 
2.0mA);   
The remote indicator does not 
illuminate in normal and flashes in 
alarm.   

Class and Setup   

Classes A1R, A2S programmable. 

Maximum Ripple 
Voltage 

2V ( peak-to-peak) 

Alarm Reset 

Instantaneous cut-out (5s Min, 
1.0VDCMax.) 

Power-up Time 

10s 

Wiring 

Polarized 2-core for loop. 
Polarized two wire for remote 
indicator. 

Ingress Protection 
Rating 

IP22 

Ambient Temperature 

Class A1: -10

~+50

 

Class A2: -10

~+50

 

Relative Humidity 

95%, non condensing 

Material of Enclosure 

ABS 

Dimensions 

Diameter: 100mm       
Height: 51.3mm (with base) 

Mounting Hole Spacing 

45mm~75mm 

Weight 

About 110g (with base) 

Accessories and Tools 

Module 

Name 

Remarks 

P-9910B 

Handheld 
Programmer 

Order separately 

DB-01 

Base 

Order separately 

DB-01D 

Base 

Order separately 

JTY-HM-GST102 

Commission Tool 

Order separately 

Limited Warranty

 

GST

 warrants that the product will be free from defects in design, 

materials  and  workmanship  during  the  warranty  period.  This 

warranty shall not apply to any product that is found to have been 

improperly  installed  or  used  in  any  way  not  in  accordance  with 

the instructions supplied with the product. Anybody, including the 

agents, distributors or employees, is not in the position to amend 

the contents of this warranty. Please contact your local distributor 

for products not covered by this warranty. 

 

 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 