Application 

System connection is shown in Fig. 4.

 

4

2

3

1

Zener 

B

a

rr

ie

r

O-

O+

Z2

Z1

D2

D1

Circuit 

B

o

ar

d

I2

I1

O1

O2

K2

K1

4       3      2       1

5        6      7        8

I- 9332 Interface 

Intrinsically Safe

 Detector

 Detector

Manual Call Point

End

 of

 line 

re

si

sto

r

4.

7k

Ω

Hazardous Area

Safety Area 

Intrinsically Safe

Intrinsically Safe

 Detector

Intrinsically Safe

 

Fig. 4 

When the detector is to be connected with I-9332 Interface 
or  Explosion-proof 

Manual  Call  Point  in  series,  a  4.7kΩ 

end-of-line resistor connected to the end of loop.   

There  are  three  conductive  elements  on  the  base  with 
terminals.  The  bases  are  connected  in  series  with  an 
end-of-line  resistor  connected  at  the  end.  Please  note 
polarity  when  connecting  the  system  with  the  method 
shown in the above figure.   

The  interface  is  integrated  with  a  safety  barrier,  which 
shall  be  installed  in  safe  area.  The  total  number  of 
explosion-proof  devices  connected  in  the  system  shall 
not be over 10.

 

Troubleshooting 

No  alarm:  First  check  external  wiring  and  screws  when 
there  is  a  problem.  If  there  is  no  problem,  return  it  for 
repair.   
False alarm: Return it for repair.   

Maintenance 

 

The  detector  should  be  installed  just  before 
commission  and  kept  well  before  installation,  with 
corresponding  measures  taken  for  dust-proof, 
damp-proof and corrosion-proof. 

 

The  dust-proof  cover  should  not  be  removed  until 
the project is put into usage. 

 

Fire  test  should  be  done  at  least  once  every  6 
months. 

Cautions 

 

I-9332  interface  box  should  be  installed  in  safety 
area;  the  wires  of  "Safety  Area"  should  be 
separated from those of "Hazardous Area", and be 
kept a certain distance (At least 50mm). 

 

The  safety  barrier  should  be  well  grounded.  The 
screws  should  not  be  loose.  Ground  resistance 
should not be over 1

Ω . The assigned parameters in 

the  intrinsically  safe  loop  should  not  be  over  the 
specified value, that is, the capacitance distributed 
among cables should not be over 0.083

μF, and the 

inductance distributed should not be over 4.1mH. 

 

During 

maintenance, 

products 

passing 

the 

explosion-proof  test  should  not  be  replaced  and 
parts  and  structure  affecting  explosion-proof 
functions should not be modified. 

 

 

 
 

Specification 

Detector Class 

P (A1R and BS can be set, factory 
default is A1R) 

Operating Voltage 

16VDC

28VDC 

Static Current 

≤60μA    (Note:  In  standby  state, 
the  detector  can  work  within 
16VDC~28VDC) 

Alarm Current 

10mA

≤I≤30mA  (

Warning:  The 

alarm  current  depends  on  the 

current limit of the FACP. It’s not 
allowed  to  power  the  detector 
directly  by  24VDC.  Otherwise 
the  detector  will  be  blown  as  a 
result of without current limiting 
resistor.

 

Maximum  Ripple 
Voltage 

4V (peak-to-peak) 

Alarm Reset 

Instantaneous  Power-off  (5s  Min, 
2.5VDC Max) 

Power-up Time 

≤10s 

Alarm Indicator 

Red. 

Flashes 

in 

polling. 

Illuminates when fire is reported. 

Explosion-proof 
Mark 

ExibIICT6 Gb 

Explosion-proof 
Certificate No. 

CE12.2146 

Safety 

Barrier 

Parameters 

U

0

=28V,  I

0

=93mA,  C

0=

0.083

F, 

L

0=

4mH, Um:250V

 

Wiring 

Polarity-sensitive, 

two-wire 

for 

connecting with power supply

 

Operating 
Environment 

Temperature:   
A1R:  typical  temperature  is  25

ranging -10

℃~

+50

 

BS :  typical  temperature  is  40

ranging -10

℃~

+65

 

Relative 

Humidity 

≤95%, 

non-condensing 

Dimensions 

Diameter:  100mm  Height  53.3mm 
(with base) 

Ingress Protection 
Rating 

IP33 

Material 

and 

Color 

of 

the 

Enclosure 

ABS

surface resistance

≤10

9

Ω

 

Weight 

About 130g 

Mounting 

Hole 

Spacing 

45mm

75mm 

Accessories and Tools 

Model 

Name 

Remark 

I-9332 

Interface 

Order separately 

DB-01(IS)  Base 

Order separately 

Limited Warranty 

GST

 warrants that the product will be free of charge for 

repairing  or  removing  from  defects  in  design,  materials 
and  workmanship  during  the  warranty  period.  This 

warranty doesn’t cover any product that is found to have 
been  improperly  installed  or  used  in  any  way  not  in 
accordance  with  the  instructions  supplied  with  the 
product.  Anybody,  including  the  agents,  distributors  or 
employees, is not in the position to amend the contents 
of this warranty. Please contact your local distributor for 
products not covered by this warranty.

 

 
 
 
 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 