Digital Flame Proof Reflective Beam Detector
Installation and Operation Manual
The Intelligent Solution
12
Fig. 10 for terminals.
K11
K12
K22
K21
D2
D1
Z2
Z1
Fig. 10
If the detector does not connected with GST fire alarm control panel,
D1 and D2 are to be connected with 24VDC power cable
polarity-insensitively, K11 and K12 are used as volt-free fire alarm
output contact, and K21 and K22 volt-free fault output contact, as in Fig.
11.
Fig. 11
(3)
Connect the earth cable to the earth point on the housing.
(4)
Connect the ribbon cable of the detector body to XT4 on the
interface board on the base, and then install the detector body onto
the base. Make sure the location element on the base in align with
the U-shaped groove on the detector body.
(5)
Secure the body with the base with the 4 Allen screws.
(6)
After installation, double-check the following: If there is cracks or
holes on the surface of the housing; if the base and detector body
Wiring hole for
24VDC Power supply
Wiring hole for
contact signal