C-9105R
Conventional Reflective Beam Detector
Installation and Operation Manual
The Intelligent Solution
6
V Mounting
and
Wiring
1
Ambient Conditions for Installation
The detector works on light obscuration principle. Avoid any
fixed or moving obscuration in its optical pathway when
installing.
The wall for mounting either the detector or the reflector should
be firm and smooth. The detector is mounted vertical to the wall.
The wall may seem to be smooth, but corrugated or uneven, or
may be changed by the environment (in rainy season or in
winter) and the installer should ensure the detector not affected
by these factors. If the detector is installed on sustaining rack
similar to metal tube, make sure the sustaining rack fixed firmly.
Not Fit for Locations where:
¾
Space height is over 40m.
¾
It is not roofed.
¾
Space height is less than1.5m.
¾
There are a lot of dust, powder or vapor.
¾
It is clean normally, but can be dusty in some special cases.
¾
Where temperature is high.
Note:
Temperature at top
part of a workshop with transparent roof may be over
50
℃
when there is sunshine.
¾
There is no access to maintenance.
¾
The mounting wall or fitting is greatly affected by
mechanical vibration.
¾
There are fixed or moving objects within 1m from the
detector’s optical pathway.
E-MAIL: [email protected]