GSM SMS Alarm Messenger
Pro X (Premium)
21
11.9)
SMS Alarm Message Setup
Alarm Channel 1 ~ 8
Command: PWD:
XXXX
,ALM
Y
TEXT:
□□□□□□□□□□□□
#%
XXXX Password
Y
Alarm Channel Number (1~8)
□□□□□□□
SMS Message (max. 130 characters)
Example:
PWD:1234,ALM4TEXT:DoorContact1Open#%
Password:
1234
Alarm Channel 4 is triggered, SMS Message “Door Contact 1 Open” is sent to
the pre-defined mobile phone numbers.
AD Channel 1 ~ 2
Command: PWD:
XXXX
,ACH
Y
TEXT:
□□□□□□□□□□□□
#%
XXXX Password
Y
AD Channel Number (0~2)
0: Low Power Input Voltage Level Alarm
1: AD Channel 1 Alarm
2: AD Channel 2 Alarm
□□□□□□□
SMS Message (max. 100 characters)
Example:
PWD:1234,ACH2TEXT:High Temperature Alert#%
Threshold
High:
4.250
AD
value:
5.123
Password:
1234
Date:
2007-06-12
Time:
19:23
AD value captured is higher than threshold high, so alert SMS is sent with the
following message content.
High Temperature Alert >ST:001;TM:28/01/2008,15:45;INPU AD2
ALARM!;A2:5.123.