GSM SMS Alarm Messenger
Pro X (Premium)
17
SMS Pro Duo automatically reports the unit health status on pre-defined schedule via
SMS message.
[SMS Message received]
ST:XXX;T:2006/10/08/06:15;V:XXXX;AI1:0000:AI2:0000:K1:X;K2:X;K3:X;K4:X;K5
:X;K6:X;K7:X;K8:X;OUT1:1:OUT2:1;OUT3:1;#.
ST
Unit Serial Number
XXX
ASCII code
T
Unit Internal Clock
XXXX
year/month/day/time
V Operating
Voltage
XXXX
AI1
A/D Channel 1
X
hex digits
AI2
A/D Channel 2
X
hex digits
K1
Alarm Channel 1
K2~8
Alarm Channel 2~8
K1:0 means “Open”
K1:1 means “Closed”
OUT1 Relay Output 1
OUT2~3 Relay Output 2~3
OUT1:0
means
“Open”
OUT1:1
means
“Closed”
Example
[SMS Message received]:
ST:001;2005/01/27/12:00;V:8.14;AI1:2312;AI2:2131;K1:1;K2:0;K3:0;K4:1;O:1
SMS Unit Current Status
ST Unit
Serial
Number
001
TIME
Unit Internal Clock
Date: 27 Jan 2005
Time: 12:00
V Operating
Voltage
8.14VDC
AI1 A/D
Channel
1
2132
AI2 A/D
Channel
2
X2131
K1
Alarm Channel 1
1
Closed
K2
Alarm Channel 2
0
Open
K3
Alarm Channel 3
0
Open
K4
Alarm Channel 4
1
Closed
O
Output Relay 1
1
ON
11.5)
Power Up Message
Whenever the unit is power up, the unit will automatically send the message “RESTART”
to control centre configured in
command 4
.
RESTART!