6
PNEG-1712
FFI SCR Replacement Kit Instructions
2. Installation
Replacing the Woods Board
1. Disconnect the power to the circuit.
2. For ease of re-connection, record the colors and terminal numbers of all wires leading to the woods
board. Disconnect wiring and remove board. Mount the new SCR board in approximately the same
location, oriented as shown in
. Note that additional holes must be drilled into
the mounting surface using a 9/64" drill bit.
3. Mount the DIN Rail (D03-0013-BRK) next to the new SCR board if possible using a 9/64" drill bit.
Use the self-tapping screws to secure the DIN Rail to the panel. Snap the power supply (GT3-0971
or D03-0805) onto the DIN Rail.
4. Reconnect the wires as follows:
Previous Woods Terminal
New SCR Terminal
Previous Woods Terminal
New SCR Terminal
L1
L1
1
S3
L2
L2 (230)
2
S2
F1
F1
3
S1
F2
F2
6
B1
A1
A1
7
B3
A2
A2